Cpu Bus Unit Area - Omron NSJ CONTROLLERS - 03-2008 Operation Manual

Nsj controllers
Table of Contents

Advertisement

I/O Memory
6-3-1

CPU Bus Unit Area

Forcing Bit Status
CPU Bus Unit Area
Initialization
1,2,3...
IOM Hold Bit Operation
The CPU Bus Unit Area contains 400 words with addresses ranging from
CIO 1500 to CIO 1899. Words in the CPU Bus Unit Area are allocated to the
built-in DeviceNet Section, CJ-series CPU Bus Units, and the following
Expansion Units: NSJ Controller Link Unit and NSJ Ethernet Unit. These
words are used to transfer data such as operating status. Each CPU Bus Unit
is allocated 25 words based on its unit number, as shown in the following
table.
Data is exchanged with CPU Bus Units once each cycle during I/O refreshing,
which occurs after program execution. (Words in this data area cannot be
refreshed with immediate-refreshing or IORF(097).)
Unit number
Allocated words
0
CIO 1500 to CIO 1524
1
CIO 1525 to CIO 1549
2
CIO 1550 to CIO 1574
3
CIO 1575 to CIO 1599
4
CIO 1600 to CIO 1624
5
CIO 1625 to CIO 1649
6
CIO 1650 to CIO 1674
7
CIO 1675 to CIO 1699
8
CIO 1700 to CIO 1724
9
CIO 1725 to CIO 1749
A
CIO 1750 to CIO 1774
B
CIO 1775 to CIO 1799
C
CIO 1800 to CIO 1824
D
CIO 1825 to CIO 1849
E
CIO 1850 to CIO 1874
F
CIO 1875 to CIO 1899
The function of the 25 words depends upon the CPU Bus Unit being used. For
details, refer to the Unit's operation manual.
Words in the CPU Bus Unit Area that aren't allocated to CPU Bus Units can
be used only in the program.
Bits in the CPU Bus Unit Area can be force-set and force-reset.
The contents of the CPU Bus Unit Area will be cleared in the following cases:
1. The operating mode is changed from PROGRAM to RUN or MONITOR
mode or vice-versa.
2. The NSJ Controller's power supply is cycled.
3. The CPU Bus Unit Area is cleared from a Programming Device (i.e., the
CX-Programmer).
4. NSJ Controller operation is stopped when a fatal error other than an
FALS(007) error occurs. (The contents of the CPU Bus Unit Area will be
retained when FALS(007) is executed.)
If the IOM Hold BIt (A50012) is ON, the contents of the CPU Bus Unit Area
won't be cleared when a fatal error occurs or the operating mode is changed
from PROGRAM mode to RUN/MONITOR mode or vice-versa. It will still be
cleared if the power supply is cycled.