Precautions
!WARNING
Serious injury may possibly occur due to breakdown of
safety outputs.
Do not connect loads beyond the rated value to the safety
outputs.
Serious injury may possibly occur due to loss of required
safety functions.
Wire G9SX properly so that supply voltages or voltages
for loads do NOT touch the safety inputs accidentally or
unintentionally.
Serious injury may possibly occur due to damages of
safety inputs.
Apply protection circuitry against back electromotive
force in case connecting inductive loads to safety outputs.
Serious injury may possibly occur due to loss of safety
functions. Use devices appropriate for the application and
the condition where G9SX is used.
Control Devices
Emergency stop switch
Use approved devices with Direct
Opening
Mechanism complying with IEC/EN
60947-5-1
Door interlocking switch
Use approved devices with Direct
Opening
Limit switch
Mechanism complying with IEC/EN
60947-5-1 and capable of switching
micro loads of 24VDC, 5mA.
Safety Sensor
Use approved devices complying with
the relevant product standards,
regulations and rules in the country
where it is used.
Consult a certification body to assess
that the entire system satisfies the
required safety category level.
Relay with forcibly guided
Use approved devices with forcibly
contacts
guided contacts complying with EN
50205. For feedback purpose use
devices with contacts capable of
switching micro loads of 24VDC, 5mA.
Contactor
Use contactors with forcibly guided
mechanism to input the signal to
Feedback/Reset input of G9SX through
the NC contact of the contactor. For
feedback purpose use devices with
contacts capable of switching micro
loads of 24VDC, 5mA. Failure to open
contacts of a contactor cannot be
detected by monitoring its auxiliary NC
contact without forcibly guided
mechanism.
Other devices
Evaluate whether devices used are
appropriate to satisfy the requirements
of safety category level.
Requirements
■ Precautions for Safe Use
1. Use G9SX within an enclosure with IP54 protection or higher of
IEC/EN60529.
2. Incorrect wiring may lead to loss of safety function. Wire
conductors correctly and verify the operation of G9SX before
commissioning the system in which G9SX is incorporated.
3. Do not apply DC voltages exceeding the rated voltages, or any
AC voltages to the G9SX power supply input.
4. Use DC supply satisfying requirements below to prevent electric
shock.
• DC power supply with double or reinforced insulation, for
example, according to IEC/EN60950 or EN50178 or a
transformer according to IEC/EN61558.
• DC supply satisfies the requirement for class 2 circuits or limited
voltage/current circuit stated in UL 508.
5. Apply properly specified voltages to G9SX inputs.
Applying inappropriate voltages cause G9SX to fail to perform its
specified function, which leads to the loss of safety functions or
damages to G9SX
6. Auxiliary error outputs and auxiliary monitoring outputs are NOT
safety outputs. Do not use auxiliary outputs as any safety output.
Such incorrect use causes loss of safety function of G9SX and its
relevant system.
Also Logical connection outputs can only be used for logical
connections between G9SXs.
7. After installation of G9SX, qualified personnel should confirm the
installation, and should conduct test operations and maintenance.
The qualified personnel should be qualified and authorized to
secure the safety on each phases of design, installation, running,
maintenance and disposal of system.
8. A person in charge, who is familiar to the machine in which G9SX
is to be installed, should conduct and verify the installation.
9. Turn OFF the signal to Safety input or Logical AND connection
input every 24hours and make sure G9SX operates without faults
by checking the state of the ERR indicator.
10.Do not dismantle, repair, or modify G9SX. It may lead to loss of its
safety functions.
11.Use only appropriate components or devices complying with
relevant safety standards corresponding to the required level of
safety categories.
Conformity to requirements of safety category is determined as
an entire system.
It is recommended to consult a certification body regarding
assessment of conformity to the required safety level.
12.OMRON shall not be responsible for conformity with any safety
standards regarding to customer's entire system.
13.Disconnect G9SX from power supply when wiring, to prevent
electric shock or unexpected operation.
14.Be cautious not to have your fingers caught when attaching
terminal sockets to the plugs on G9SX.
15.The lifetime of G9SX depends on the conditions of switching of its
outputs. Be sure to conduct its test operation under actual
operating conditions in advance and use it within appropriate
switching cycles
16.Do not use in combustible gases or explosive gases. Arcs or heat
generated by switching elements of G9SX can lead to fire or
explosion.
Flexible Safety Unit
G9SX