■ Wiring of Inputs and Outputs
Signal name
Terminal name
Power supply input
A1, A2
Safety input 1
T11, T12
Safety input 2
T21, T22
Feedback/reset input T31, T32, T33
Logical AND
T41, T42,
connection input
T51, T52
Cross fault detection
Y1
input
Instantaneous safety
S14, S24, S34
output
OFF-delayed safety
S44, S54
output
Logical connection
L1, L2
output
Auxiliary monitor
X1
output
Auxiliary error output X2
10
Flexible Safety Unit
Description of operation
The input terminals for power supply.
Connect the power source to the A1 and A2
terminals.
To set the safety outputs in the ON state, the HIGH
state signals must be input to both safety input 1 and
safety input 2. Otherwise the safety outputs cannot
be in the ON state.
To set the safety outputs in the ON state, the ON
state signal must be input to T33.
Otherwise the safety outputs cannot be in the ON
state.
To set the safety outputs in the ON state, the signal
input to T32 must change from the OFF state to the
ON state, and then to the OFF state. Otherwise the
safety outputs cannot be in the ON state.
A logical AND connection means that one unit (Unit
A) outputs a safety signal "a" to a subsequent unit
(Unit B) and Unit B calculates the logical
multiplication (AND) (i.e., outputs the AND) of the
signal "a" and safety signal "b", which is input to Unit
B.
Thereby the logic of the safety output of Unit B is "a"
AND "b". (An AND of inputs "a" and "b" is output.)
To set the safety outputs of the subsequent Unit in
the ON state, its logical AND connection preset
switch must be set to AND (enable) and the HIGH
state signal must be input to T41 of the subsequent
unit.
Selects the mode for the failure detecting (cross fault
detecting) function for the safety inputs of G9SX
corresponding to the connection of the cross fault
detection input.
Turns ON/OFF according to the state of the safety
inputs, feedback/reset inputs, and logical AND
connection inputs.
During OFF-delay state, the Instantaneous safety
outputs are not able to turn ON.
OFF-delayed safety outputs.
The OFF-delay time is set by the OFF-delay preset
switch.
When the delay time is set to zero, these outputs can
be used as non-delay outputs.
Outputs a signal of the same logic as the
instantaneous safety outputs.
Outputs a signal of the same logic as the
instantaneous safety outputs
Outputs when the error indicator is lit or blinking.
G9SX
Wiring
Connect the power supply plus (24 VDC) to the A1
terminal.
Connect the power supply minus (GND) to the A2
terminal.
Corresponds to
Safety Category
2
T11 T12 T21 T22
Corresponds to
Safety Category
3
T11 T12 T21 T22
Corresponds to
Safety Category
4
T11 T12 T21 T22
Auto reset
T31
Manual reset
Reset
Switch
T31
Input a
Unit A
G9SX-BC202 or
G9SX-AD322-T
L1 A2
Output (a)
Logical AND connection sig. (1st layer)
Input b
Unit B
T41 T42
G9SX-AD322-T
L1
A2
Output (a&b)
Logical AND connection sig. (2nd layer)
T41 T42
G9SX-AD322-T
L1
A2
Next unit (5 layers max.)
Keep Y1 open when using T11, T21. (Wiring
corresponding to category 4)
Connect Y1 to 24 VDC when not using T11, T21.
(Wiring corresponding to category 2 or 3, or when
connecting safety sensors)
Keep these outputs open when not used.
Keep these outputs open when not used.
Keep these outputs open when not used.
Keep these outputs open when not used.
Keep these outputs open when not used.
+24 V
+24 V
Y1
+24 V
+24 V
+24 V
Y1
NC
Y1
Feedback loop
KM
+24 V
T32
T33
Feedback loop
KM +24 V
T32
T33
Next unit (4 unit max.)
T41 T42
G9SX-AD322-T
Next unit (4 unit max.)