Expansion Unit
Item
Rated load
Rated carry current
Maximum switching voltage
■ Characteristics
Item
Over-voltage category (IEC/EN 60664-1)
Operating time (OFF to ON state)
(See note 1.)
Response time (ON to OFF state)
(See note 1.)
ON-state residual voltage
OFF-state leakage current
Maximum wiring length of safety input and
logic AND input
Reset input time (Reset button pressing time) 100 ms min.
Accuracy of OFF-delay time (See note 5.)
Insulation
Between logical AND connection
resistance
terminals, and power supply
input terminals and other input
and output terminals connected
together
Between all terminals connected
together and DIN rail
Dielectric
Between logical AND connection
strength
terminals, and power supply
input terminals and other input
and output terminals connected
together
Between all terminals connected
together and DIN rail
Between different poles of
outputs
Between safety relay outputs
connected together and other
terminals connected together
Vibration resistance
Mechanical
Destruction
shock
Malfunction
resistance
Durability
Electrical
Mechanical
Ambient temperature
Ambient humidity
Terminal tightening torque (See note 6.)
Weight
Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times
and response times, respectively, of all the Units connected by logical AND.
2. Represents the operating time when the safety input turns ON with all other conditions set.
3. Represents the operating time when the logical AND input turns ON with all other conditions set.
4. This does not include the operating time or response time of Advanced Units that are connected.
5. This does not include the operating time or response time of internal relays in the G9SX-EX-@.
6. For the G9SX-@-RT (with screw terminals) only.
4
Flexible Safety Unit
G9SX-EX-@
250 VAC, 3A/30 VDC, 3A (resistive load)
3 A
250 VAC, 125 VDC
G9SX-AD322-@/ADA222-@
II
50 ms max. (Safety input: ON)
(See note 2.)
100 ms max. (Logical AND
connection input: ON) (See
note 3.)
15 ms max.
3.0 V max. (safety output, auxiliary output)
0.1 mA max. (safety output, auxiliary output)
100 m max.
(External connection impedance: 100 Ω max. and 10 nF max.)
Within ± 5% of the set value
20 M Ω min. (by 100 VDC
megger)
500 VAC for 1 min
---
Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
2
300 m/s
2
100 m/s
---
---
− 10 to 55 ° C (no icing or condensation)
25% to 85%
0.5 N·m
Approx. 200 g
G9SX
G9SX-BC202-@
50 ms max. (Safety input: ON) 30 ms max. (See note 4.)
---
---
20 M Ω min. (at 100 VDC)
---
500 VAC for 1 min
---
Approx. 125 g
G9SX-EX-@
II (Safety relay outputs 13 to
43 and 14 to 44: III)
10 ms max. (See note 4.)
Within ± 5% of the set value
---
100 M Ω min. (at 500 VDC)
---
1,200 VAC for 1 min
2,200 VAC for 1 min
100,000 cycles min.
(rated load, switching
frequency: 1,800 cycles/hour)
5,000,000 cycles min.
(switching frequency: 7,200
cycles/hour)
Approx. 165 g