Omron G3ZA - MANUAL 2 User Manual page 88

Multi-channel power controller
Hide thumbs Also See for G3ZA - MANUAL 2:
Table of Contents

Advertisement

Level
Variable
Address
type
Opera-
C1 (81)
0024
tion
0025
0026
0027
0028
0029
002A
002B
002C
C3 (83)
0000
0001
0002
0003
0004
0005
0006
0007
0008
0009
000A
000B
000C
000D
000E
000F
71
Parameter name
CT1 SSR short-circuit
H'00000000 to H'000000A5 (0 to 165)
detection value
CT2 SSR short-circuit
H'00000000 to H'000000A5 (0 to 165)
detection value
CT3 SSR short-circuit
H'00000000 to H'000000A5 (0 to 165)
detection value
CT4 SSR short-circuit
H'00000000 to H'000000A5 (0 to 165)
detection value
CT1 heater overcurrent
H'00000000 to H'000000A5 (0 to 165)
detection value
CT2 heater overcurrent
H'00000000 to H'000000A5 (0 to 165)
detection value
CT3 heater overcurrent
H'00000000 to H'000000A5 (0 to 165)
detection value
CT4 heater overcurrent
H'00000000 to H'000000A5 (0 to 165)
detection value
Offset control
H'00000000 (Disabled)
H'00000001 (Enabled)
Communications data
H'00000000 (7)
length (See note 1.)
H'00000001 (8)
Communications stop bits
H'00000000 (1)
(See note 1.)
H'00000001 (2)
Communications parity
H'00000000 (Note)
(See note 1.)
H'00000001 (Even)
H'00000002 (Odd)
Communications send
H'00000000 to H'00000063 (0 to 99)
standby time (See note 1.)
Communications timeout
H'00000000 (Disabled)
time (See note 1.)
H'00000001 to H'0000003C (1 to 60)
Operation at error
H'00000000 (Continue with error clear)
H'00000001 (Continue with no error clear)
H'00000002 (Stop) (See note 2.)
Offset value
H'00000000 to H'000003E8 (0.0 to 100.0)
Hysteresis
H'00000001 to H'0000000A (1 to 10)
SSR drive selection (See
H'00000000:
note 1.)
H'00000001:
H'00000002:
Current monitor display
H'00000000 (0 to 50 A)
selection (See note 1.)
H'00000001 (0 to 150 A)
H'00000002 (0% to 100%)
Control switchover hystere-
H'00000000 to H'0000012C (0.0 to 30.0)
sis (See note 1.)
Communications timeout
H'00000000 (Disabled)
time 2 (See note 1.)
H'00000001 to H'00000E10 (1 to 3600)
CT1 assignment (See
H'00000000 (Disabled)
note 1.)
H'00000001 (ch1)
H'00000002 (ch2)
CT2 assignment (See
H'00000003 (ch3)
note 1.)
H'00000004 (ch4)
CT3 assignment (See
note 1.)
CT4 assignment (See
note 1.)
Setting/monitor range
SSR for single-phase heater with zero-cross
function:Optimum cycle control
SSR for single-phase heater without zero-
cross function: Soft-start optimum cycle
control
SSR for three-phase heater with zero-cross
function: Three-phase optimum cycle con-
trol
Appendix
V2
Default
Unit
165
A or %
165
A or %
165
A or %
165
A or %
165
A or %
165
A or %
165
A or %
165
A or %
1
---
7
bit
2
bit
1
---
1
ms
0
min
0
---
20.0
%
1
A or %
0
---
0
---
1.0
%
0
s
1
---
2
---
3
---
4
---