Monitoring Total Run Time

5-8

Monitoring Total Run Time

The total run time monitor function is used to calculate the total time that
power is ON to the G3PW Power Controller and to output an alarm when the
time reaches the preset value in the Total Run Time Alarm Set Value parame-
ter [P16]. This function can be used for maintenance and managing equip-
ment by presetting replacement times for devices, such as heaters, in the
Total Run Time Alarm Set Value parameter.
Operation during an alarm output is set in the Total Run Time Exceeded
Operation parameter [P15] in the initial setting level.
P15 setting
0
No operation
The alarm does not operate.
1
Alarm level 1
An alarm is output to the ALARM1 contacts and operation is
stopped.
2
Alarm level 2
An alarm is output to the ALARM2 contacts and operation
continues.
The total run time exceeded alarm is set in the Total Run Time Alarm Set
Value parameter [P16] in the initial setting level.
P16 setting range
0.0 to 99.9 kh (0.0: Operation stopped)
The total run time is cleared by the Initialize Set Values parameter [P27] in the
initial setting level.
P27 setting
0
Do not initialize.
1
Initialize
Use the Total Run Time Monitor parameter (POT) in the monitor level to mon-
itor the present total run time.
Meaning
Meaning
Section 5-8
57