Specifications

■ Ratings
Input (at an Ambient Temperature of 25°C)
Model
Rated voltage
G3NA-2@@B-UTU 5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
G3NA-4@@B-UTU 5 to 24 VDC
100 to 240 VAC
G3NA-275B-UTU
5 to 24 VDC
G3NA-290B-UTU
100 to 240 VAC
G3NA-475B-UTU
G3NA-490B-UTU
G3NA-D210B-UTU
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120 VAC,
the input impedance is measured at 120 VAC).
2. With constant current input circuit system.
3. Refer to Temperature Characteristics (for Must Operate Voltage and Must Release Voltage) in Engineering Data for further details.
Output
Model
Rated load voltage Load voltage range
G3NA-205B-UTU
24 to 240 VAC
G3NA-210B-UTU
G3NA-410B-UTU
200 to 480 VAC
G3NA-220B-UTU
24 to 240 VAC
G3NA-425B-UTU
200 to 480 VAC
G3NA-240B-UTU
24 to 240 VAC
G3NA-250B-UTU
24 to 240 VAC
G3NA-450B-UTU
200 to 480 VAC
G3NA-275B-UTU
24 to 240 VAC
G3NA-475B-UTU
200 to 480 VAC
G3NA-290B-UTU
24 to 240 VAC
G3NA-490B-UTU
200 to 480 VAC
G3NA-D210B-UTU 5 to 200 VDC
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data.
2. When an OMRON Heat Sink (refer to Options) or a heat sink of the specified size is used.
Operating voltage
Impedance
(See note 1.)
4 to 32 VDC
15 mA max. (See note 2.) 4 VDC max.
36 k Ω± 20%
75 to 132 VAC
72 k Ω± 20%
150 to 264 VAC
4 to 32 VDC
7 mA max. (See note 2.)
72 k Ω± 20%
75 to 264 VAC
4 to 32 VDC
15 mA max. (See note 2.) 4 VDC max.
72 k Ω± 20%
75 to 264 VAC
With heat sink
(See note 2.)
0.1 to 5 A (at 40 ° C)
19 to 264 VAC
0.1 to 10 A (at 40 ° C)
0.2 to 10 A (at 40 ° C)
180 to 528 VAC
0.1 to 20 A (at 40 ° C)
19 to 264 VAC
0.2 to 25 A (at 40 ° C)
180 to 528 VAC
0.1 to 40 A (at 40 ° C)
19 to 264 VAC
0.1 to 50 A (at 40 ° C)
19 to 264 VAC
0.2 to 50 A (at 40 ° C)
180 to 528 VAC
1 to 75 A (at 40 ° C)
19 to 264 VAC
1 to 75 A (at 40 ° C)
180 to 528 VAC
1 to 90 A (at 40 ° C)
19 to 264 VAC
1 to 90 A (at 40 ° C)
180 to 528 VAC
0.1 to 10 A (at 40 ° C)
4 to 220 VDC
Must operate voltage
75 VAC max. (See note 3.) 20 VAC min. (See note 3.)
150 VAC max. (See note 3.) 40 VAC min. (See note 3.)
4 VDC max.
75 VAC max.
75 VAC max.
Applicable load
Load current (See note 1.)
Without heat sink
0.1 to 3 A (at 40 ° C)
0.1 to 4 A (at 40 ° C)
0.2 to 4 A (at 40 ° C)
0.1 to 4 A (at 40 ° C)
0.2 to 4 A (at 40 ° C)
0.1 to 6 A (at 40 ° C)
0.1 to 6 A (at 40 ° C)
0.2 to 6 A (at 40 ° C)
1 to 7 A (at 40 ° C)
1 to 7 A (at 40 ° C)
1 to 7 A (at 40 ° C)
1 to 7 A (at 40 ° C)
0.1 to 4 A (at 40 ° C)
Solid State Relays
Voltage level
Must release voltage
1 VDC min.
1 VDC min.
20 VAC min.
1 VDC min.
20 VAC min.
Inrush current
60 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
800 A (60 Hz, 1 cycle)
800 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
20 A (10 ms)
G3NA
3