22. PARAMETERS
Ress(inputhpcssiMe
at any time.
Reset
input
is possible
parameter
unit
is
0
X
Operation continues if !he
1
o n l y w h e n h
protection
0
0
disconnected
function is
activated.
Reset
input
is
possible
at any time.
Reset
input
is posslMe
1unetit-m i s activated
0
x
When the parameter
unit
i s
disconnected. the
ALARM
LED
is lit and inverter
output is shut otf.
3
only
when
h
proteaion
0
Operation continues
If
the
parameter unit is
disconnected.
Reset inpuf
is possible
When the parameter unit
is
disconnected, the ALARM
LED is
lit
and invener
output is shut
off.
Reset input is possible
17
oniy when
the
protection
lunction
is
activated.
0:
Yes
x : No
No
function in
Ext
mode.
When
stop
key on
PU
is
pressed
in any
operation
m o d e ,
m t o r
stops.
(Note
2)
Notrr:
1. If the circuit across terminals
RES
and SD is closed while the inverter is operating,
the inverter shuts ofl the output while the terminals are closed. The data related
to
the electronic thermal relay and the regenerative brake duty ratio is cleared and the
motor lree wheels.
2. Procedure
for
restarting after stopping with the parameter unit stop key in
Ext
mode.
(1) After the inverter has stopped, turn
off
the start signal (STFISTR).
(2) Press t h e parameter unit's external operation key.
(3) Switch ON the start command (STF/STR).
Apart from the procedure above, oepration can also be restarted by switching the
power
off
and
back
on, or by resetting the inverter by closing the circuit across the
reset terminals.
3. When operation is stopped in external mode using the parameter unit stop key, 'EO"
is displayed on the parameter unit.
I
L b CAUTION
I
I
L ? L
With
the
start signal input, do not reset
the
inverter.
After reset, the inverter will start instantaneously. creating a hazardous condition.
I
- 8 5 -