11. OPERATION
11.8 LocaVAuto External Signal Selection Mode
In this mode, the operation mode can be modified
by
turning ON/OFF an external signal (terminal
RH). Since the operation
mode
can
be
changed by the external signal, erroneous mode switching
can be avoided.
Set
Signal
value
(RH
and
SD)
Flxsd
mode
Comment
I
~
1
Close
I
mode
External
o p e r a t m
1
Changing
to the PU
operation mode is impossible.
I
8
Open
Changing
to
the
external operation
mode is
PU
operation
mode
impo~ible,
If the circuk a c w terminals RH and SD is closed while in the PU operation mode, the operation
mode is forcibly changed to the external operation mode. If it is opened, the operation mode is
forcibly changed to the PU operation mode.
Note that this
mode
change is possible only while the inverter is stopped. The
mode
change is
not allowed while the inverter is operating.
Note:
If
'8'
is set for Pr.79, the function of the terminal RH (multiple speed setting (high-speed))
is changed to the locaVauto external selection function. In this setting, the ordinary func-
tion of the terminal RH does not work.