STEP-BY-STEP STARTING OF THE UNIT
In order to guarantee easy and complete starting up, here is the order of the different key stages that must be
carried out:
-
Electrical connection of the power supply to the 400 V three-phase system.
-
Pneumatic connection of the oil separator pressure reducer.
-
Connection of the remote control with the UI screen.
-
UI screen configuration and setup.
Connection to the main
— Three-phase 400V. power supply without neutral–
50 Hz
— Compressed air supply 5 Bars minimum.
Recommendations
Part nos of
electrical
cables
(kW)
15
18.5
22
37
45
55
1- Electricity supply :
The power supply is to be connected to the terminals of the main disconnector on the side panel of the unit.
Use multi-conductor cable suited to the power of the unit and connect the three phases to the three terminals of the
disconnector and the earth to the earth bar provided.
-16
MAINS VOLTAGE 50 Hz
230V
230 3PH
single
phase
Section (mm²)
All the operations relating to the installation,
such as those for assembly, putting into service
and maintenance, are to be carried out by
qualified personnel under the control of a
responsible technician
Part nos of electrical cables
Cable section
3x1.5 mm²
400
3x2.5 mm²
3PH
4x2.5 mm²
4x4 mm²
4x4
4x6 mm²
4x6
4x10 mm²
4x10
4x16 mm²
4x16
4x25 mm²
4x25
4x35 mm²
4x25
8695 8420 / A
.
Part no
W000010098
W000010099
W000010100
W000010101
W000010102
W000010103
W000010104
W000010105
W000010106
CCHD