Dometic FreshJet FJX Service Manual page 18

Roof air conditioner
Hide thumbs Also See for FreshJet FJX:
Table of Contents

Advertisement

Available languages

Available languages

EN   Dometic FJX
6. Disconnect the quick connector from the process pipe.
7.
Test the welding points for refrigerant leakages (see
Testing for refrigerant leaks
Using a refrigerant leak detector
Observe the following when using a refrigerant leak detector:
• The use of silicone sealants may reduce the effectiveness of leak detectors. Intrinsically safe components do
not need to be isolated before working.
• Ensure that the sensitivity of the refrigerant leak detector has been calibrated.
• Ensure that the refrigerant leak detector has been calibrated in a refrigerant free area.
• Ensure that the refrigerant leak detector is set to a percentage of the low flammable limit of the refrigerant.
• Ensure that the refrigerant leak detector is set to the refrigerant present in the roof air conditioner.
• Ensure that the corresponding gas percentage is set to a maximum of 25 %.
1.
Switch the refrigerant leak detector on.
Follow the refrigerant leak detector manufacture's instructions.
2. Move the refrigerant leak detector 1 ... 3 mm away from the weldings.
3. Move the probe around the welding.
4. If a refrigerant leak has been detected, drain the refrigerant (see
5. Solder the leak.
18
Using a refrigerant leak detector
Draining the refrigerant
on page 18).
on page 15).