Filling the refrigerant
NOTICE! Damage hazard
• Only fill the roof air conditioner with the refrigerant specified on the data plate
page 29).
• Ensure that no debris enters the refrigerant circuit when filling refrigerant.
• Do not overfill the refrigeration circuit.
NOTE
The filling quantity must correspond to the refrigerant quatity stated in the technical (see
page 29).
1.
Connect a refrigerant filling machine suitable for flammable refrigerant to the quick connector.
Follow the refrigerant filling machine manufacture's instructions.
2. Make the appropriate settings on the refrigerant filling machine.
Follow the refrigerant filling machine manufacture's instructions.
3. Fill refrigerant into the refrigerant circuit.
4. Disconnect the refrigerant filling machine.
5. Weld the process pipe using welding spot pliers.
Follow the welding spot pliers manucature's instructions.
Dometic FJX EN
(Technical data
on
Technical data
on
17