Installer Test Mode; Dehumidification Only; Zoning And/Or Ventilation - Aprilaire E080 Installation & Owner's Manual

80 & 100 ppd professional-grade, whole-house dehumidifiers
Hide thumbs Also See for E080:
Table of Contents

Advertisement

INSTALLER TEST MODE

If everything is properly wired, the dehumidifier and all of the
wired components will turn on and off during Installer Test
Mode to demonstrate that all are properly operating Installer
Test Mode lasts for four (4) minutes If the ON/OFF button is
pressed during test mode, the dehumidifier will exit Installer
Test Mode and return to the OFF screen

DEHUMIDIFICATION ONLY

If the dehumidifier is not already OFF, press the ON/OFF button
to turn it off
Press and hold the ON/OFF and MODE buttons for 3 seconds
The measured humidity, AIR SAMPLING and TEST will show on
the display If wired to the HVAC system, the HVAC blower will
turn on and if there is/are damper(s) wired to the DEH DAMPER
terminals of the control, the damper(s) will energize
After three (3) minutes the dehumidifier compressor will turn on
and DEHUMIDIFYING will replace AIR SAMPLING on the control
screen
18
90-1854
90-1854
90-1854
After one minute of compressor operation, all outputs will turn
off and DONE will blink for 3 seconds and then return to the OFF
screen

ZONING AND/OR VENTILATION

If the dehumidifier has been set up for ventilation, VENTILATING
will appear on the display throughout Installer Test Mode, and
the ventilation damper will be energized
If the dehumidifier has been set up for zoning, PRIMARY ZONE
will show on the display for the first minute of dehumidifier
blower operation After one minute, SECONDARY ZONE will show
on the display and the zone dampers will de-energize
90-1854
90-1854
90-1854
90-1854