2.5.1 Connecting High Ac/Dc Power - Siemens SIMATIC NET RUGGEDCOM RX1510 Equipment Manual

Rugged multi service platforms
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RX1510:
Table of Contents

Advertisement

Installing the Device
2.5.1 Connecting High AC/DC Power
Power modules can be equipped with either a screw or European-style (Euroblock)
terminal block. The screw terminal block is installed using Phillips screws and
compression plates, allowing either bare wire connections or crimped terminal lugs.
For information about installing or removing a power module, refer to "Installing/
Removing Power Modules" (Page 30).
Electrocution hazard – risk of serious personal injury or death
The device may have two power modules equipped, which may be connected to
separate power sources. Make sure all power sources are off before servicing the
power module terminals.
2.5.1
Connecting High AC/DC Power
To connect a high AC/DC power supply to the device, do the following:
Electrocution hazard – risk of death, serious personal injury and/or damage to
the device
Make sure the supplied cover is always installed over high voltage screw terminal
blocks.
12
DANGER
NOTICE
In a high AC/DC and low DC (24/48 V) power module arrangement, the
placement of the AC and DC power supplies is not slot-dependent. Either power
module slot can be used for AC or DC power.
For maximum redundancy in a dual power module configuration, use two
independent power sources.
Use minimum #16 gage copper wiring when connecting terminal blocks.
The maximum wire length between the terminal block and power source must
not exceed 6 m (20 ft) for 24 V power supplies or 18 m (60 ft) for 48 V power
supplies.
For 125/230 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker
must be installed.
It is recommended to provide a 20 A circuit breaker for the power module.
Equipment must be installed according to applicable local wiring codes and
standards.
DANGER
RUGGEDCOM RX1510
Equipment Manual, 10/2023, C79000-G8976-1055-25

Advertisement

Table of Contents
loading

Table of Contents