IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
IEC 60255-5
a
Siemens-specified severity levels.
EMC Immunity Type Tests for IEEE 1613
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RX1510
Equipment Manual, 10/2023, C79000-G8976-1055-25
Test
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
and Interrupts
Damped Oscillatory
Mains Frequency
Voltage
Ripple on DC
Power Supply
Voltage Dips
and Interrupts
Dielectric Strength
HV Impulse
Description
HV Impulse
6.2 EMC and Environmental Type Tests
Description
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Enclosure Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
DC Power Ports
DC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
Certification
Test Levels
± 2 kV Line-to-Line
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
100 A/m, continuous
1000 A/m for 1 s
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay output)
1.5 kV
2 kV
5 kV (Failsafe Relay output)
5 kV
Test Levels
5 kV (Failsafe Relay Output)
Severity
Levels
3
4
3
a
Note
5
3
4
3
43