Installing the Device
2.5.1 Connecting High AC/DC Power
It is recommended to provide a 20 A circuit breaker for the power module.
Equipment must be installed according to applicable local wiring codes and
standards.
2.5.1

Connecting High AC/DC Power

To connect a high AC/DC power supply to the device, do the following:
DANGER
Electrocution hazard – risk of death, serious personal injury and/or damage to
the device
Make sure the supplied cover is always installed over high voltage screw terminal
blocks.
CAUTION
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to a 12, 24 or 48 VDC power supply terminal block.
Damage to the power supply may occur.
Note
The screw terminal block is installed using Phillips screws and compression plates, al-
lowing either bare wire connections or crimped terminal lugs. Use #6 size ring lugs
for secure, reliable connections.