Refrigerant Piping - Lennox 10ACC-018 User Manual

Ac system information for homeowner / user
Table of Contents

Advertisement

Refrigerant Piping

Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, non-
flare) series line sets as shown in table 1 or use field-fabri-
cated refrigerant lines. Refer to Refrigerant Piping Guide
(Corp. 9351−L9) for proper size, type, and application of
field−fabricated lines. Valve sizes are also listed in table 1.
Table 1
Refrigerant Line Kits
Valve Field Size
Connections
Model
Model
Name
Liquid
Vapor
Line
Line
3/8 in
5/8 in
−018
(10 mm)
(16 mm)
−024
3/8 in
3/4 in.
−030
(10 mm)
(19 mm)
−036
−042
3/8 in
7/8 in.
−048
(10 mm)
(22 mm)
−060
3/8 in
1−1/8 in.
(10 mm)
(29 mm)
NOTE − Units are designed for line sets of up to 50 feet (15
m). For applications longer than 50 feet, consult the Len-
nox Refrigerant Piping Guide (Corp. 9351−L9). Select line
Recommended Line Set
L15
Liquid
Vapor
Line Sets
Line
Line
L15−21
5/16 in*
5/8 in
15 ft.− 50 ft.
(8 mm)
(16 mm)
(4.6m − 15m)
L15−41
3/8 in
3/4 in.
15 ft.− 50 ft.
(10 mm)
(19 mm)
(4.6 m − 15m)
3/8 in
7/8 in.
L15−65
(10 mm)
(22 mm)
15 ft.− 50 ft.
(4.6 m − 15m)
3/8 in
1−1/8 in.
Field
(10 mm)
(29 mm)
Fabricated
set diameters from table 1 to ensure that oil returns to the
compressor.
*Use reducer from bag assembly.
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is
important to properly isolate the refrigerant lines to prevent
unnecessary vibration. Line set contact with the structure
(wall, ceiling or floor) causes some objectionable noise
when vibration is translated into sound. As a result, more
energy or vibration can be expected. Closer attention to
line set isolation must be observed.
Following are some points to consider when placing and
installing a high−efficiency outdoor unit:
1- Placement − Be aware some localities are adopting
sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmis-
sion.
2- Line Set Isolation − The following illustrations demon-
strate procedures which ensure proper refrigerant line
set isolation. Figure 4 shows how to install line sets on
vertical runs. Figure 5 shows how to install line sets on
horizontal runs. Figure 6 shows how to make a transition
from horizontal to vertical. Finally, figure 7 shows how to
place the outdoor unit and line set.
Page 5

Advertisement

Table of Contents
loading

This manual is also suitable for:

10acc-02410acc-03010acc 03610acc 04210acc 04810acc 060

Table of Contents