Setting The Unit; Electrical - Lennox 10ACC-018 User Manual

Ac system information for homeowner / user
Table of Contents

Advertisement

Setting the Unit

CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
CAUTION
Sharp sheet metal edges can cause injury. When
installing the unit, avoid accidental contact with
sharp edges.
Refer to unit dimensions for sizing mounting slab, plat-
forms or supports. Refer to figure 1 for installation clear-
ances.
Installation Clearances
36
(914 mm)
*NOTE − A service clearance of 30" (762 mm) must be main-
tained on one of the sides adjacent to the control box. Clear-
ance to one of the other three sides must be 36" (914 mm).
Clearance to one of the remaining two sides may be 12" (304
mm) and the final side may be 6" (152 mm).
NOTE − A clearance of 24" (610 mm) must be maintained
between two units.
NOTE − 48" (1219 mm) clearance required on top
of unit. Maximum soffit overhang is 36" (914 mm).
Figure 1
Slab Mounting
When installing unit at grade level, install on a level slab
high enough above grade to allow adequate drainage of
water. Top of slab should be located so run−off water from
higher ground will not collect around unit.
Roof Mounting
Install the unit at a minimum of 4 inches (102 mm) above
the surface of the roof. Ensure the weight of the unit is prop-
36
(914 mm)
36*
(914 mm)
36*
(914 mm)
erly distributed over roof joists and rafters. Redwood or
steel supports are recommended.

Electrical

In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
Unit must be grounded in accordance with
national and local codes.
Electric Shock Hazard.
Can cause injury or death.
1 Install line voltage power supply to unit from a properly
sized disconnect switch.
2 Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is in the bottom of
the control box. Connect conduit to the control box us
ing a proper conduit fitting.
NOTE − Units are approved for use only with copper
conductors.
24V, Class II circuit connections are made in the low
voltage junction box. Refer to figure 2 for field wiring
diagram.
NOTE − A complete unit wiring diagram is located in
side the unit control box cover.
3 Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations.
4 Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit. See figure 3.
Page 3
WARNING

Advertisement

Table of Contents
loading

This manual is also suitable for:

10acc-02410acc-03010acc 03610acc 04210acc 04810acc 060

Table of Contents