System Operation; Maintenance - Lennox 10ACC-018 User Manual

Ac system information for homeowner / user
Table of Contents

Advertisement

Normal Operating Pressures In psig (liquid and vapor +/− 2 psig)*
Out. Coil
Unit /
Entering
Entering
Metering
Metering
Air Temp.
Device
LIQ.
5F (5C)
65 (18.3)
153
75 (23.9)
180
85 (29.4)
209
10ACC /
10ACC /
95 (35.0)
240
TXV
TXV
105 (40.6)
274
110 (43)
292
115 (45)
311
65 (18.3)
155
75 (23.9)
182
85 (29.4)
211
10ACC /
95 (35.0)
242
fixed orifice
fixed orifice
105 (40.6)
274
110 (43)
291
115 (45)
308
*These are typical pressures only. Indoor indoor match up, indoor air quality, and indoor load will cause the pressures to vary.

System Operation

The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switch is
in the ON position, the indoor blower operates continuously.

Maintenance

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
season, the system should be checked as follows:
WARNING
Electric shock hazard. Can cause inju-
ry or death. Before attempting to per-
form any service or maintenance, turn
the electrical power to unit OFF at dis-
connect switch(es). Unit may have
multiple power supplies.
1 − Clean and inspect the outdoor coil. The coil may be
flushed with a water hose. Make sure power is off be-
fore cleaning.
2 − Condenser fan motor is prelubricated and sealed. No
further lubrication is needed.
3 − Visually inspect connecting lines and coils for evidence
of oil leaks.
4 − Check wiring for loose connections.
−018
−024
SUC.
LIQ.
SUC.
LIQ.
71
163
70
175
72
193
71
206
73
225
72
241
77
260
73
277
79
298
74
316
80
318
75
336
81
338
75
357
62
165
63
181
68
194
67
211
72
224
70
242
77
257
73
276
80
293
76
313
81
313
78
332
83
332
79
353
Table 7
−030
−036
SUC.
LIQ.
SUC.
LIQ.
76
162
70
173
77
187
74
201
78
219
75
234
80
253
77
269
81
291
79
307
82
310
80
326
83
329
81
346
69
168
67
178
73
195
71
202
76
224
75
235
79
255
78
270
81
289
82
308
82
305
83
326
84
324
84
347
5 − Check for correct voltage at unit (unit operating).
6 − Check amp−draw condenser fan motor.
Unit nameplate _________ Actual ____________ .
NOTE − If the owner complains of insufficient cooling,
the unit should be gauged and the refrigerant charge
should be checked. Refer to the charging section in
this instruction.
Indoor Coil
1 − Clean coil, if necessary.
2 − Check connecting lines and coils for evidence of oil
leaks.
3 − Check the condensate pan line and clean it if necessary.
Indoor Unit
1 − Clean or change filters.
2 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
3 − Belt Drive Blowers − Check belt for wear and proper
tension.
4 − Check all wiring for loose connections
5 − Check for correct voltage at unit (blower operating).
6 − Check amp−draw on blower motor
Unit nameplate_________ Actual ____________.
Page 15
−042
−048
SUC.
LIQ.
SUC.
LIQ.
73
159
71
170
74
188
72
201
74
220
73
234
75
251
76
270
76
290
77
309
77
309
78
331
78
328
79
351
67
163
68
189
70
190
71
203
71
220
74
233
74
251
77
265
78
288
79
301
79
307
80
319
80
325
82
339
−060
SUC.
74
76
77
79
79
80
81
72
74
77
79
82
83
84