Toshiba MMY-MUP0961HT6P-UL Service Manual page 99

Hide thumbs Also See for MMY-MUP0961HT6P-UL:
Table of Contents

Advertisement

The 'Night operation can be set by a number of remote controls. It operates according to the start time
and the end time set by each remote controls.
No.1 Indoor unit RC
Night operation Start/End time
No.2 Indoor unit RC
Night operation Start/End time
Outdoor unit
Night operation
If the 'Night operation' time set by a number of remote controls overlaps, it starts at the start time set
• •
by any one of the remote controls, and ends when all remote controls reach the end time.
No.1 Indoor unit RC
Night operation Start/End time
No.2 Indoor unit RC
Night operation Start/End time
Outdoor unit
Night operation
The 'Night operation' with remote controls, and the 'Night Operation Control' with optional control
• •
P.C.board (TCB-PCMO4E) connected to the outdoor unit, can be used together. The outdoor unit
operates in 'Night Operation' when either control is effective.
TCB-PCMO4E
Night operation Control OFF
RC Night operation
Start/End time
Outdoor unit
Night operation
12:00
13:00
Start
End
ON
OFF
19:00
Start
ON
OFF
ON
ON
20:00
Start
ON
OFF
22:00
06:50
Start
End
22:00
End
21:00
07:00
Start
End
OFF
22:50
End
- 99 -