Toshiba MMY-MUP0961HT6P-UL Service Manual page 176

Hide thumbs Also See for MMY-MUP0961HT6P-UL:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Sub-code
P.C.board
P.C.board
Compressor Fan Motor
Compressor Fan Motor
1
2
1
2
1
2
01
O
11
O
02
O
12
O
03
O
O
13
O
O
08
O
18
L29
09
O
O
19
O
0A
O
O
1A
O
0B
O
O
O
1B
O
O
10
O
Circle (O): Trouble P.C. board
00
L30 Detected indoor unit No.
P03
01: Compressor 1
P04
02: Compressor 2
00: Power detection trouble
01: Open phase
P05
00 : Compressor 1 or 2 heat sink trouble
01 : Compressor 1 heat sink trouble
02 : Compressor 2 heat sink trouble
P07
04: Heat sink dewing
P10 Indoor unit No. detected
P11
P13
01: Outdoor unit valve is close
P14
01: TS condition
P15
02: TD condition
P17
P19 Outdoor unit No. detected
P20
Display of receiving unit
Central
Indicator light block
control or
main remote
Operation Timer Ready
controller
display
1
2
O
O
O
L29
O
O
O
O
O
O
O
O
L29
(L30)
P03
P04
P05
P07
(P10)
P11
P13
P14
P15
P17
P19
P20
Typical problem site
Flash
Trouble in number of
SIM
P.C. boards
The number of P.C. board
SIM
trouble
Indoor external trouble
SIM
input (interlock)
Outdoor discharge (TD1)
ALT
temperature trouble
Activation of high-pressure
ALT
SW
Power detection trouble
/Open phase detection
ALT
Heat sink overheating
trouble
ALT
Heat sink dewing trouble
ALT
Indoor unit overflow
Outdoor heat exchanger
ALT
freeze trouble
Outdoor liquid backflow
ALT
detection trouble
Another refrigerant cycle
ALT
protection
ALT
Gas leak detection
Outdoor discharge (TD2)
ALT
temperature trouble
4-way valve reversing
ALT
trouble
Activation of high-pressure
ALT
protection
- 176 -
Description of Check code
There are insufficient number of P.C. board in
inverter box.
When there is much number of an inverter P.C.
board to model setting of an interface P.C. board.
Indoor unit has been shut down for external
trouble input in one refrigerant line (detected by
indoor unit).
Outdoor discharge temperature sensor (TD1) has
detected abnormally high temperature.
High-pressure SW is activated.
Open phase is detected when power is turned on.
Temperature sensor built into IPM (TH) detects
overheating.
Outdoor liquid temperature sensor (TL2) has
detected abnormally low temperature.
Indoor unit has been shutdown in one refrigerant
line due to detection of overflow (detected by
indoor unit).
Remaining frost on outdoor heat exchanger
has been detected repeatedly.
State of refrigerant cycle circuit indicates liquid
backflow operation.
Outdoor unit valve is forget to open during test
run.
Outdoor suction temperature sensor (TS1) detects
sustained and repeated high temperatures that
exceed standard value.
Outdoor discharge temperature sensor (TD2)
detects abnormally high temperature.
Abnormality in refrigerating cycle is detected
during heating operation.
High pressure (Pd) sensor detects high pressure
that exceeds standard value.