No.
Item
2) By setting the CODE No. 06, the setup temperature
3
Room temp.
control
(Continued)
4
Automatic
1) Based on the difference between TA and Ts, the
capacity control
35.6(+2)
33.8(+1)
30.2(–1)
5
Automatic
1) The judgment of selecting COOL/HEAT is carried out as
cooling/heating
control
2) For the automatic capacity control after judgment of
3) For temperature compensation of room temp. control in
Outline of specifications
in heating operation can be compensated.
Setup data
0
32˚F(+0C˚)
Setup temp. compensation
The initial factory default value
Model
Floor standing cabinet, Floor standing concealed,
Floor standing
Other models
operation capacity is determined by the outdoor unit.
COOL
TA
˚F(˚C)
SD
SB
S9
S7
Ts
S5
S3
S0
shown below. When TA exceeds Tsh by 1.5 for 10
minutes, the operation is thermostat OFF then, the
heating operation (thermostat OFF) is changed to
cooling operation.
TA
Cooling
˚F(˚C)
34.7(+1.5)
Tsc
or
Tsh
(Cooling OFF)
29.3(-1.5)
Description in the parentheses shows an example of
cooling ON/OFF.
When TA is less than Tsh by 1.5 for 10 minutes, the
operation is thermostat OFF then, the cooling
operation (thermostat OFF) is changed to heating
operation.
cooling/heating, refer to item No.4.
automatic heating, refer to item No.3.
2
4
6
36˚F(+2C˚) 39˚F(+4C˚) 43˚F(+6C˚)
Set data
0
2
HEAT
TA
˚F(˚C)
33.8(+1)
S3
S0
S5
Ts
S7
S9
30.2(–1)
SB
SD
38.4(–2)
SF
(Cooling ON)
Heating
- 63 -
Remarks
Return air temperature
shift of heating operation
Except while sensor of
the remote controller is
controlled
(Code No. [32], "0001")
Ts: Setup temp.
TA: Room temp.
∗ For Heat recovery
system outdoor unit
type
Tsc: Setup temp. in
cooling operation
Tsh: Setup temp. in
heating operation +
temp. compensation
of room temp. control