Note 1: Criteria for the difference between suction and discharge temperatures
(1) Cooling operation
After operating for a minimum of 30 minutes in "COOL" mode, if the T dry bulb temperature difference
between suction and discharge air of the indoor unit is 46.4°F(8°C) or more, it is normal.
(2) Heating operation
After operating for a minimum of 30 minutes in "HEAT" mode, if the T dry bulb temperature difference
between suction and discharge air of the indoor unit is 59°F(15°C) or more, it is normal.
* If demand from the indoor unit on the outdoor unit is low because the difference between the temperature
set by the remote controller and the temperature of the room is small, then the T temperature difference is
small.
* Consider that T temperature difference may diminish in cases of a system in which the connected indoor
unit capacity exceeds the outdoor unit capacity, the pipe length is long, or a large difference exists among
outdoor units.
Note 2: Criteria for operating power current
The table below shows the maximum current for each outdoor unit. Under standard conditions, operating
current is about 80% of the value shown in the table below.
Model
MMY-MUP
Current value
(A)
Model
MMY-MUP
Current value
(A)
Note 3: Criteria for cycle status
(1) These data are based on operating a 4-way Air Discharge Cassette type air conditioner of 100%
connection with standard piping length.
Data may vary depending on temperature conditions, installed pipe length, and room shape combinations,
or indoor unit connection capacity.
For pressure criteria in different temperature conditions, refer to (2).
Outdoor
Pressure
Unit
Operating
(Psi)
MMY-
Mode
MUP
Pd
Ps
Cooling
391 145
0721*
Heating
310 102
Cooling
430 142
0961*
Heating
307
96
Cooling
419 131
1201*
Heating
321
94
Cooling
443 142
1441*
Heating
310
91
Cooling
440 139
1681*
Heating
330
91
Cooling
445 139
1921*
Heating
330
93
Cooling
383 146
072H1*
Heating
310 105
Cooling
393 140
096H1*
Heating
305 101
Cooling
402 131
120H1*
Heating
319
96
* This compressor is driven with a 6-pole motor. The value of the compressor frequency (rps) measured with a
clamp meter at the compressor lead line is three times the rotation count (rps) of the compressor.
* Each compressor may have a different frequency as a measure against resonance.
* The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling, and
TC2 sensor temperature when heating, respectively.
(2) Criteria for operating pressure
Pressure
Operating
psi (MPa)
Mode
Pd
Cooling
290.1 ~ 478.6 (2.0 ~ 3.3)
Heating
362.6 ~ 478.6 (2.5 ~ 3.3)
* Criteria after 14 minutes or more has passed since operating started
0721*
0961*
1201*
16.53
16.61
22.95
072H1*
096H1*
120H1*
15.14
17.6
23.74
Pipe Surface Temperature
(°F)
Indoor Heat
Discharge
Suction
Exchanger
TD1
TS1
TC2
166
64
55
143
37
80
178
62
55
146
34
82
181
63
55
153
34
80
183
66
57
150
31
81
186
63
57
160
32
84
189
63
56
159
28
85
166
65
55
143
37
80
167
65
56
142
37
82
178
61
56
150
34
83
PS
72.5 ~ 130.5 (0.5 ~ 0.9)
64.4 ~ 89.6 (18 ~ 32)
72.5 ~ 101.5 (0.5 ~ 0.7)
59 ~ 89.6 (15 ~ 32)
1441*
1681*
1921*
23.38
26.07
30.28
Outdoor Heat
Liquid
Compressor 1 Compressor 2
Exchanger
Temperature
TE1
TL3
103
75
33
73
104
79
32
77
108
85
32
64
108
89
32
69
108
87
33
77
108
90
31
77
101
77
34
75
104
89
33
74
103
84
32
76
Temperature
°F(°C)
Indoor
Outdoor
77 ~ 95 (25 ~ 35)
41 ~ 95 (5 ~ 35)
- 146 -
Compressor Rotation
Air Temperature
(rps)
Indoor
Fan
Outdoor Indoor
Cmp.1
Cmp.2
44
-
High
50
-
High
47/43
58
-
High
67
-
High
47/43
54
-
High
58
-
High
47/43
60
-
High
69
-
High
47/43
66
-
High
77
-
High
47/43
62
61
High
72
70
High
47/43
44
-
High
49
-
High
47/43
43
-
High
45
-
High
47/43
54
-
High
58
-
High
47/43
(DB/WB)(°F)
TO
TA
95/-
80/67
70/-
95/-
80/67
70/-
95/-
80/67
70/-
95/-
80/67
70/-
95/-
80/67
70/-
95/-
80/67
70/-
95/-
80/67
70/-
95/-
80/67
70/-
95/-
80/67
70/-