No.
Item
6
Air speed
1) By the command from remote control, fan speed is
selection
2) When the air speed mode [AUTO] is selected, the air
<COOL>
• Air speed mode [AUTO] in case when remote
controller sensor works is equal to that in case when
indoor unit sensor works.
• If the air speed has been changed once, it is not
changed for 3 minutes. However when the air volume
is changed, the air speed changes.
• When cooling operation has started, select a down-
ward slope for the air speed, that is, the high position.
• If the temperature is just on the difference boundary,
the air speed is not changed.
<HEAT>
32.9(+0.5) 33.8(+1.0)
32.0(0) Tsh
31.1(-0.5) 30.2(-1.0)
30.2(-1.0) 28.4(-2.0)
29.3(-1.5) 26.6(-3.0)
28.4(-2.0) 24.8(-4.0)
( ) : indicate the value when the remote controller
• If the air speed has been changed once, it is not
changed for 1 minute. However when the air speed
changed, the air speed changes.
• When heating operation has started, select an upward
slope for the air speed, that is, the high position.
• If the temperature is at the difference boundary, the air
speed is not changed.
• If TC2 ≥ 140˚F(60˚C), the air speed increases by
1 step.
Outline of specifications
changed. ((HH), (H+), (H), (L+), (L) or [AUTO])
speed varies by the difference between TA and Ts.
TA ˚F (˚C)
37.4(+3.0)
HH
36.5(+2.5)
<HH>
35.6(+2.0)
H+ <HH>
34.7(+1.5)
H <HH>
33.8(+1.0)
L+ <H+>
32.9(+0.5)
L <H>
Tsc
L <H>
31.1(-0.5)
L <L+>
< > : Indicate automatic cooling.
TA˚F(˚C)
L <L+>
L+ <H>
H <H+>
H+
<HH>
HH
<HH>
< > : Indicate automatic heating.
Indoor unit sensor works.
Remote controller sensor works.
sensor is worked.
A
B
C
D
E
F
G
E
D
C
B
A
- 64 -
Remarks
HH > H+ > H > L+ > L > UL
Fan speed
4-way cassette
Compact 4-way
2-way cassette
1-way cassette (SH)
Depends on fan speed mode
selection at the remote
controller. (H+) and (L+)
cannot be selected.
For Floor Standing Concealed
Type,or Floor Standing
Cabinet Type,(HH), (H), (L) or
[AUTO] can be selected
regardless of remote controller
models.
Code No. 32
0000: Indoor unit sensor
(Main unit)
0001: Remote controller
sensor
TC2: Temperature of indoor
heat exchanger sensor