Change of Set Flow and Hysteresis [Simple setting mode]

■Simple setting mode
In the simple setting mode, the set value, hysteresis and delay time can be changed while checking the
current flow value (main display).
<Operation>
[Hysteresis mode]
(1) Press the S button for 1 second or longer (but less than 3 seconds) in measurement mode. [SEt] is
displayed on the main display.
When the button is released while in the [SEt] display, the current flow value is displayed on the main
display, [P] or [n] is displayed on the sub display (left) and the set value is displayed on the sub display
(right).
(2) Change the set value using the ▲ or ▼ button, and press the SET button to set the value. Then, the
setting moves to hysteresis setting.
(The snap shot function can be used. (Refer to page 62))
(3) Change the set value using the ▲ or ▼ button, and press the S button to set the value.
(The snap shot function can be used. (Refer to page 62))
(4) Press and hold the S button for 2 seconds or longer to complete the OUT setting.
(If the button is pressed for less than 2 seconds, the setting will be returned to P.)
1: Selected items of (1) to (3) become valid after pressing the S button.
2: After enabling the setting by pressing the S button, it is possible to return to measurement mode by pressing the S button
for 2 seconds or longer.
3: When the output mode is set to error output or output OFF (refer to page 35), the simple setting mode cannot be used.
(the setting returns to measurement mode by releasing the button when [SEt] is displayed).