Systemvu Control System; Systemvu Interface; Air Temperature Sensors; Additional Systemvu Installation And Troubleshooting - Carrier 48JCH 04-06 Series Service And Maintenance Instructions

Single package rooftop ultra low nox (14 ng /j) gas heat / electric cooling unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

SYSTEMVU CONTROL SYSTEM

The SystemVu™ control is a comprehensive unit-management
system. The control system is easy to access, configure, diagnose
and troubleshoot.
The SystemVu control system is fully communicating and cable-
ready for connection to the Carrier Comfort Network
Carrier i-Vu
®
, and Third Party BACnet
systems. The control provides high-speed communications for re-
mote monitoring via the Internet. Multiple units can be linked to-
gether (and to other Direct Digital Control (DDC) equipped units)
using a 3-wire communication bus.
The SystemVu control system is easy to access through the use
of a integrated display module. A computer is not required for
start-up. Access to control menus is simplified by the ability to
quickly select from 7 main menu items. An expanded readout
provides detailed explanations of control information. Only six
buttons are required to maneuver through the entire controls
menu. The display readout is designed to be visible even in
bright sunlight (see Fig. 51).

SystemVu Interface

This integrated device is the keypad interface used to access the
control information, read sensor values, and test the unit. The in-
terface is located in the main control box.
1. Third-party trademarks and logos are the property of their respective
owners.
J2
J1
TB1
(CCN),
®
1
building management
J3A
J3B
J3C
J3D
J3E
J4
TB2
TB3
Fig. 51 — SystemVu Control
Through the SystemVu interface, the user can access all of the
inputs and outputs to check on their values and status, configure
operating parameters, and evaluate the current decision status for
operating modes. The control also includes an alarm history
which can be accessed from the display. The user can access a
built-in test routine that can be used at start-up commissioning
and troubleshooting.

Air Temperature Sensors

The SystemVu controller uses thermistors to sense temperatures
used to control operation of the unit. Air temperatures are mea-
sured with 10k thermistors. This includes supply-air temperature
(SAT), outdoor-air temperature (OAT) and return-air temperature
(RAT) sensors. See Fig. 52 for location of these sensors.
Additional SystemVu Installation and Trouble-
shooting
Additional installation, wiring and troubleshooting information
for the SystemVu Controller can be found in the following manu-
al: 48/50JC 04-06 Ultra High Efficiency Single Package Rooftop
Units with SystemVu™ Controls Version X.X Controls, Start-up,
Operation and Troubleshooting Instructions.
J5
J6
J7
J18
J20
32
J8
J9
J17
J16
J15
TB4
TB5
J10
J11
J12
J13
J14

Advertisement

Table of Contents
loading

This manual is also suitable for:

48jcg 04-06 series

Table of Contents