The high static option supply fan motor is equipped with a pilot-
circuit Thermix combination over-temperature/over-current pro-
tection device. This device resets automatically. Do not bypass
this switch to correct trouble. Determine the cause and correct it.
CONDENSER FAN MOTOR PROTECTION
The condenser fan motor is internally protected against over-
temperature.

Relief Device

A soft solder joint at the suction service access port provides
pressure relief under abnormal temperature and pressure condi-
tions (i.e., fire in building). Protect this joint during brazing op-
erations near this joint.

Control Circuit, 24-V

The control circuit is protected against overcurrent conditions
by a circuit breaker mounted on control transformer TRAN.
Reset is manual.

SYSTEMVU CONTROL SYSTEM

The SystemVu™ control is a comprehensive unit-management
system. The control system is easy to access, configure, diag-
nose and troubleshoot.
The SystemVu control system is fully communicating and
cable-ready for connection to the Carrier Comfort Network
(CCN), Carrier i-Vu
, and Third Party BACnet
®
agement systems. The control provides high-speed communi-
1. BACnet is a registered trademark of ASHRAE (American Society of
Heating, Refrigerating and Air-Conditioning Engineers).
J2
J1
TB1
®
building man-
1
J3A
J3B
J3C
J3D
J3E
J4
TB2
TB3
Fig. 51 — SystemVu Control
cations for remote monitoring via the Internet. Multiple units
can be linked together (and to other Direct Digital Control
(DDC) equipped units) using a 3-wire communication bus.
The SystemVu control system is easy to access through the use
of a integrated display module. A computer is not required for
start-up. Access to control menus is simplified by the ability to
quickly select from 7 main menu items. An expanded readout
provides detailed explanations of control information. Only six
buttons are required to maneuver through the entire controls
menu. The display readout is designed to be visible even in
bright sunlight. See Fig. 51.

SystemVu Interface

This integrated device is the keypad interface used to access
the control information, read sensor values, and test the unit.
The interface is located in the main control box.
Through the SystemVu interface, the user can access all of the
inputs and outputs to check on their values and status, config-
ure operating parameters, and evaluate the current decision sta-
tus for operating modes. The control also includes an alarm
history which can be accessed from the display. The user can
access a built-in test routine that can be used at start-up com-
missioning and troubleshooting.
Additional SystemVu Installation and Trouble-
shooting
Additional installation, wiring and troubleshooting information
for the SystemVu Controller can be found in the following
manual: "48/50FC 04-07, 48/50GC 04-06 Single Package
Rooftop Units with SystemVu™ Controls Version 1.X Con-
trols, Start-up, Operation and Troubleshooting."