PURON (R-410A) REFRIGERANT

This unit is designed for use with Puron
Do not use any other refrigerant in this system.
Puron (R-410A) refrigerant is provided in pink (rose) colored cyl-
inders. These cylinders are available with and without dip tubes;
cylinders with dip tubes will have a label indicating this feature.
For a cylinder with a dip tube, place the cylinder in the upright po-
sition (access valve at the top) when removing liquid refrigerant
for charging. For a cylinder without a dip tube, invert the cylinder
(access valve on the bottom) when removing liquid refrigerant.
Because Puron (R-410A) refrigerant is a blend, it is strongly rec-
ommended that refrigerant always be removed from the cylinder
as a liquid. Admit liquid refrigerant into the system in the dis-
charge line. If adding refrigerant into the suction line, use a com-
mercial metering/expansion device at the gauge manifold; remove
liquid from the cylinder, pass it through the metering device at the
gauge set and then pass it into the suction line as a vapor. Do not
remove Puron (R-410A) refrigerant from the cylinder as a vapor.

Refrigerant Charge

Amount of refrigerant charge is listed on the unit's nameplate. Re-
fer to Carrier GTAC2-5 Charging, Recovery, Recycling and Rec-
lamation training manual and the following procedures.
Unit panels must be in place when unit is operating during the
charging procedure.
NO CHARGE
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant.
LOW-CHARGE COOLING
Using Cooling Charging Charts, Fig. 19-24, vary refrigerant until
the conditions of the appropriate chart are met. Note the charging
charts are different from type normally used. Charts are based on
charging the units to the correct sub-cooling for the various operat-
ing conditions. Accurate pressure gauge and temperature sensing
device are required. Connect the pressure gauge to the service port
on the liquid line. Mount the temperature sensing device on the
liquid line and insulate it so that outdoor ambient temperature does
not affect the reading. Indoor-air cfm must be within the normal
operating range of the unit.
48JC(G/H) SIZE
DESIGNATION
04
05
06
EXAMPLE:
Model
Outdoor Temperature
Suction Pressure
Suction Temperature should be
USING COOLING CHARGING CHARTS
Take the outdoor ambient temperature and read the liquid pressure
gauge. Refer to chart to determine what liquid temperature should
be. If liquid temperature is low, add refrigerant. If liquid tempera-
ture is high, carefully recover some of the charge. Recheck the liq-
uid pressure as charge is adjusted.
(R-410A) refrigerant.
®
NOMINAL TONS REFERENCE
3
4
5
48JC(G/H)*B04
85°F (29°C)
140 psig (965 kPa)
65°F (16°C)
COOLING CHARGING CHARTS
R-410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Cooling test
60.0
140
Add Charge if Above the Curve
48.9
120
37.8
100
26.7
80
15.6
60
4.5
40
-6.6
20
150
200
250
1034
1379
1723
Compressor Discharge Pressure, [psig/Kpa]
Fig. 19 — Cooling Charging Chart - 3 Ton
R-410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Humidimizer test
60.0
140
Add Charge if Above the Curve
48.9
120
37.8
100
26.7
80
15.6
60
4.5
40
-6.6
20
150
200
250
1034
1379
1723
Compressor Discharge Pressure, [psig/Kpa]
Fig. 20 — Cooling Charging Chart - 3 Ton with
Humidi-MiZer
12
3 Ton JC
compressor speed to 4400)
Remove Charge if Below the
Curve
300
350
400
450
500
550
2068
2413
2758
3102
3447
3792
48TC004277 REV -
3 Ton JC Humidimizer
compressor speed to 4400)
Remove Charge if Below the
Curve
300
350
400
450
500
550
2068
2413
2758
3102
3447
3792
48TC004274 REV -
®
System Option
600
4136
600
4136