Carrier 48JCH 04-06 Series Service And Maintenance Instructions page 72

Single package rooftop ultra low nox (14 ng /j) gas heat / electric cooling unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

PRESSURES
Gas Inlet Pressure in. wg
Gas Manifold Pressure
Refrigerant Suction
Refrigerant Discharge
Verify Refrigerant Charge using Charging Charts
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped)
Verify smoke detector unit shutdown by utilizing magnet test
IV. HUMIDI-MIZER
®
SYSTEM START-UP
STEPS
1. Check UCB (Unit Control Board) for jumper 1, 2, 3 (Jumper 1, 2, 3 must be cut and open)
2. Open humidistat contacts
3. Start unit In cooling (Close Y1)
OBSERVE AND RECORD
A. Suction pressure
B. Discharge pressure
C. Entering air temperature
D. Liquid line temperature at outlet or reheat coil
E. Confirm correct rotation for compressor
F. Check for correct ramp-up of outdoor fan motor as condenser coil warms
4. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed
5. Check unit charge per charging chart
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected)
B. Discharge pressure unchanged
C. Liquid temperature drops to 50 to 55°F range
D. LSV solenoid energized (valve closes)
6. Switch unit to dehumid (reheat) by opening Y1
OBSERVE
A. Suction pressure increases to normal cooling level
B. Discharge pressure decreases (35 to 50 psi) (Limited by head pressure control)
C. Liquid temperature returns to normal cooling level
D. LSV solenoid energized (valve closes)
E. DSV solenoid energized, valve opens
7. With
unit
in
LSV and DSV solenoids de-energized
8. Open W1 restore unit to dehumid mode
9. Open
humidistat
LSV and DSV solenoids de-energized
10. Restore set points for thermostat and humidistat
© 2023 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480306-01
STAGE 1
STAGE 2
dehumid
mode
close
input
compressor
Printed in U.S.A.
Form 48JCG-4-6-01SM
____________ in. wg
____________ in. wg
____________ in. wg
____________ psig
____________ psig
(Y/N) _______
W1
compressor
and
and
outdoor
Pg CL-2
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
_____________ psig
_____________ psig
______________ °F
______________ °F
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
outdoor
fan
stop;
(Y/N) _____
(Y/N) _____
fan
stop;
(Y/N) _____
(Y/N) _____
11-23
Replaces: NEW