Commissioning
6.5 Local commissioning
Button
With the successful completion of each quick commissioning wizard, the following are set:
• Units set in the wizard are applied to device display and fieldbus
• Sensor damping is set per wizard parameter "Response rate", and all other damping (local
display, current output, fieldbus) is set to zero (disabled).
• Process value per application (Level, Space, Distance, Volume, Volume flow) is set as the
source for:
– "Current output (HART)" - channel 1 (CH1) (if HART communication card installed), and
– "Current output 2" - channel 3 (CH3) for measurement point 2
• Process value per application are used in operation view: "View 1" and "View 3"
• Additionally, for Volume flow application:
– Volume flow is used as the source, and sets units for totalizers
– "View 2" uses Head as the source for "Totalizer 1" (TOT1)
– "View 4" uses Head as the source for "Totalizer 3" (TOT3)
A successfully completed pump control, basic control or alarms wizard does not set any
views, or other parameters, external to the wizard.
54
Function
Leave menu without saving changes
Scroll up in list of options
Scroll down in list of options
Select option.
Confirm selection and save setting.
"Current output 1" - channel 2 (CH2) for measurement point 1
- "Totalizer 1" (TOT1) and "Totalizer 2" (TOT2) on measurement point 1
- "Totalizer 3" (TOT3) and "Totalizer 4" (TOT4) on measurement point 2
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA