Sensor Connections - Siemens SITRANS L Compact Operating Instructions

Controllers with ultrasonic transducer inputs
Table of Contents

Advertisement

Connecting
5.2 Connecting SITRANS LT500
5.2.1

Sensor connections

Hazardous voltage
Hazardous voltage present on transducer terminals during operation.
Note
Important wiring notes
• Do not connect coaxial cable directly to the device due to high voltage transmitted on
shield of coaxial cable; use coaxial cable converter box instead (see wiring below).
• Do not connect the device shield and white transducer wires together; wire to separate
terminals.
• Disregard older transducer manuals that recommend these practices.
Coaxial cable converter wiring
Note
Improper installation in hazardous areas
Coaxial cable converter is available with approvals for ordinary location applications.
• Do not install in hazardous areas.
32
To sensor (measurement point 1)
Note that for EchoMax transducer connection:
positive = black wire
negative = white wire
WARNING
SITRANS LT500 with ultrasonic transducer inputs
Compact Operating Instructions, 02/2024, A5E52021877-AA