3.4 SICAM FSI Mounting

Mounting SICAM FSI using Hot Stick (Telescopic) with Device Adaptor

3.4.3
To mount the device on the MV overhead line with telescopic hot stick, proceed as follows:
!
DANGER
Warning due to live voltage when mounting the device.
Non-observance of the following measures leads to death or serious injury.
Mounting the device or replacing the device must be carried out by trained personnel (see preface)
²
and must observe the safety requirements and precautions.
Before mounting the device, ensure that you wear safety helmet, gloves and boots. It is recommended
²
to use sunshields while working in bright sunny environment.
Siemens recommends using the telescopic hot stick (Make: Ritz, VTT-1/9 or equivalent) with a
²
minimum isolation of 125 kV AC. Follow safety measures and recommended maintenance proce-
dures as per the hot stick (telescopic) supplier.
Ensure that the hot stick is dry and clean from dirt before mounting or unmounting the device on
²
the MV overhead line.
Do not mount and unmount the device from the MV overhead line if the weather is wet, if it is
²
raining, if there is a fog, or if snow is falling.
Do not rest or hang telescopic hot stick with device unattended on the MV overhead line.
²
Assign 1 device per phase.
Open both hooks of the device.
[le_sfsi_hookopen, 1, --_--]
Figure 3-12
(1)
32
Opening the Hooks of the Device
Hooks
SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual