2 Engineering
2.3.3

Assign PROFINET device names to the ET 200SP

For the CPU to be able to communicate with the distributed I/O, the ET 200SP
must also be assigned a PROFINET device name.
1. Open the "Network view" in the TIA Portal by clicking "Devices & networks" in
the project tree.
2. Open the shortcut menu for the ET 200SP by right-clicking on the ET 200SP
figure.
3. Select "Assign device name" from the shortcut menu.
4. Select the respective "Online access" and click "Update list".
5. Select the appropriate ET 200SP from the list and click "Assign name".
Figure 2-7: Assign PROFINET device names
6. Close the menu with "Close".
Inductive clocking sensor
Entry ID: 109818998,
V1.0,
05/2023
20