9.6.3 Horizontal Intake and Exhaust
Termination
End
Cap
End
Cap
End Cap
9.6.4 Direct Vent Application –
Horizontal Installation
Exhaust Gas
In cases where a 12" horizontal clearance is not
possible, provide a vertical clearance of at least
36" with the exhaust above the intake but do not
exceed 20' .
Exhaust
Maximum
length
Intake
20' (6 m)
Minimum
length
36" (91 cm)
Exhaust
Note
Intake Air
Exhaust
Intake
The illustration is intended for
reference purposes only.
Direct the exhaust away from any
building openings.
During cold weather situations, the
temperature of the exhaust will be
much warmer than the ambient air.
Therefore, you will see water vapor
being produced at the termination.
Installing a Common Vent System
Maximum
length 20'
(6 m)
Minimum
length 36"
(91 cm)