Item
Turn on or turn off the
boiler pump in DHW
18. Boiler pump
mode.
Oper(DHW)
Turn on or turn off the
system pump in DHW
19. Sys pump
mode.
Oper(DHW)
Turn on or turn off Zone 2
pump in DHW mode.
20. Zone2 pump
Oper(DHW)
Turn on or turn off the
DHW pump in DHW
mode when both the
21. DHW pump
space heating and DHW
Oper(DHW pri)
demands are present.
Set the space heating
pump over-run time.
22. Boiler Pump
Delay**
When the DHW
temperature sensor is
used:
23. DHW Demand
On Diff
When the DHW
temperature sensor is
used:
24. DHW Demand
Off Diff
Set the heat exchanger's
protection level.
25. HEX Protection
Level
Description
Setting range: On/Off
Default: Off
Setting range: On/Off
Default: Off
Setting range: On/Off
Default: Off
Setting range: On/Off
Default: On
Setting range: 3 – 40 min
Default: 40 min
Setting range: 0–10°C
(0–18°F)
Default: 3°C (5°F)
Setting range: 0–5°C
(0–9°F)
Default: 0°C (0°F)
Setting range: 0–5 Level
Default: 4 Level
The HEX
Note
Protection Level
Settings only
applies to the
NHB-H boilers.
Item
Set the time for service
notification.
26. Service Notif
Time
Set the service
notification according to
the operating times.
27. Service Notif Cycl
View the service contact
28. Service contact #
information.
Initialize all parameter
settings (panel and main
29. Factory Reset
controller) to factory
default.
Change the parameter
setting password.
Rotate the Command dial
30. P/W Change
(
and places, and press the
Command dial (
save the new password.
If you enter an incorrect password 10
Note
times or make no inputs 5 minutes,
the boiler will return to Normal mode.
To return to the previous mode, press
the Reset button.
The Factory default password is "1234".
If you make no inputs for 10 seconds
in the Parameter Edit mode, the
current parameter value will be saved
automatically.
Press and hold the Back button (
in Parameter Edit mode for 5 seconds
to reset individual parameters to their
default values.
When you reset one of the following
parameters, the corresponding
parameter will be reset automatically:
- Supply Min or Max capacity limit
- Return Min or Max capacity limit
Description
Setting range: 30 –
3650 days (10 years)
It can be set in 10 day
increments.
Default: 1820 days (5
years)
Setting range: 300 –
36500 cycles
It can be set in 100
cycle increments.
Default: 18200 cycles
) to change numbers
) to
)
Operating the Boiler
113