3.5.5 System Application - DHW System with Indirect Tank (Primary/Secondary Piping)
Make-up Water
Backflow Preventer
Pressure Reducing Valve
DHW
Outlet
DHW Inlet
System application drawings are intended to explain the system piping concept only.
Note
●
Install a filter in the system return to remove foreign objects from the system. Foreign objects inside
●
the system may result in abnormal system operation.
Refer to "3.3 Filling the System" on page 26 for make-up water connections and refer to the
●
requirements of your local codes to ensure compliance.
Use a pump with an integral check valve or install a check valve at the pump outlet.
●
Refer to the "3.6.10 Wiring Diagram - DHW System with Indirect Tank" on page 43 for wiring
●
connections.
System Pump
Air Separator
Expansion Tank
Anti-scald Mixing Valve
Indirect Tank
Boiler Pump
DHW Pump
Installing the System Piping
33