Thermistors Indoor; Thermistors Outdoor - GE AZ45E07EA Series Technical Service Manual

2016 zoneline air conditioner
Table of Contents

Advertisement

Thermistors Indoor

All 265 volt Zoneline models have two indoor
thermistors which are attached to the indoor coil,
and an outlet air thermistor attached to the air
The indoor air thermistor is mounted on the front of
the coil to sample the incoming room air.
The indoor coil thermistor is mounted on the right
side of the coil in a copper well to sample the coil
temperature.
The outlet air thermistor is mounted on the air
Indoor Thermistor Resistance (ohms)
°F
AIR
10
63,260
30
34,620
32
32,860
50
19,970
70
11,950
90
7,320

Thermistors Outdoor

All Zoneline heat pump models have two outdoor
thermistors.
One outdoor thermistor is attached to the outdoor
coil, and one outdoor thermistor is set into the
base assembly, enabling it to monitor outdoor air
temperature.
Outdoor Thermistors Resistance (ohms)
°F
AIR
10
28030
30
15340
32
14570
50
8850
70
5300
90
3280
– 34 –
COIL
OUTLET
94,900
296,800
51,940
169,800
49,330
161,500
29,960
99,480
17,930
59,700
10,970
36,990
COIL
28030
15340
14570
8850
5300
3280