Component Checks at Main Board

Thermistors
Indoor Fan Motor
Outdoor Fan Motor
ICR Pump
Thermal fuse/In-line fuse
Reversing Valve Coil
Heaters (230/208 models)
NOTE: ALL RESISTANCES SHOWN ARE APPROXIMATIONS
INDOOR
J29 pin 1 and pin 2 AIR range 7k ohms to 64k ohms
Pin 3 and pin 4 COIL range 10.5k ohms to 95k ohms
Pin 5 and pin 6 OUTLET range 35k ohms to 300k ohms
OUTDOOR
J30 pin 1 and pin 2 AIR range 3k ohms to 28.5k ohms
Pin 4 and pin 5 COIL range 3k ohms to 28.5k ohms
*
J2 pin 1 and pin 2 blue
Pin 3 and pin 4
to black 38.5k ohms approximately
pin 3 through pin 6
pin 4 through 6 black to red
*
J3 pin 1 and pin 2 blue to
Pin 3 and pin 4
to black 47k ohms approximately
Pin 3 through pin 6
approximately
Pin 4 through pin 6 black to red
J23 pin 1 and pin 2
models)
J21 pin 1 to black on Capacitor .001 ohms
J22 pin 1 to pin 2 blue to blue ~ 3.23k ohms (265 models)
Plug blue to
on relay 26 ohms
Plug
to
on relay 46 ohms
Plug
to
on relay 65 ohms
– 29 –
to red
to red 8meg ohms
to
~ 335 ohms (265