when temperature is below 50°F.
The make up air module will turn on when the
outdoor relative humidity is above 55%, and turns
is done by the outdoor humidistat located on the
module.
If troubleshooting the make up air module with an
amp probe, the amperage should be between 3/4's
and 1 amp, measured on the blue wire of the make
up air module harness. This is dependent upon the
line voltage.