Electrical Service

VOLTAGE

The maximum allowable voltage variation is ±10% of the
rated voltage on the ice machine model/serial number plate
at start-up (when the electrical load is highest).
The 115/1/60 ice machines are factory pre-wired with an 8'
power cord and NEMA 5-15P-plug configuration.
The 208-230/1/60 and 230/50/1 ice machines are factory
pre-wired with an 8' power cord only, no plug is supplied.

FUSE/CIRCUIT BREAKER

A separate fuse/circuit breaker must be provided for each ice
machine.

ELECTRICAL SPECIFICATIONS

Ice Machine
Voltage Phase Cycle
UF0140
UF0190
UF0240
UF0310
12
Maximum Fuse/
Circuit Breaker
115/1/60
208-230/1/60
230/1/50
115/1/60
208-230/1/60
230/1/50
115/1/60
208-230/1/60
230/1/50
115/1/60
208-230/1/60
230/1/50

TOTAL CIRCUIT AMPACITY

The total circuit ampacity is used to help select the wire size
of the electrical supply.
The wire size (or gauge) is also dependent upon location,
materials used, length of run, etc., so it must be determined
by a qualified electrician.

GROUND FAULT CIRCUIT INTERRUPTER

Ground Fault Circuit Interrupter (GFCI/GFI) protection is a
system that shuts down the electric circuit (opens it) when it
senses an unexpected loss of power, presumably to ground.
Manitowoc does not recommend the use of a GFCI/GFI
circuit protection with our equipment. If code requires the
use of a GFCI/GFI, then you must follow the local code. The
circuit must be dedicated, sized properly, and there must be
a panel GFCI/GFI breaker. We do not recommend GFCI/GFI
outlets, as they are known for more intermittent nuisance
trips than panel breakers.
Air-Cooled
Total Amps
15
5.0
15
2.5
15
2.5
15
6.0
15
3.0
15
2.5
15
7.0
15
3.5
15
4.0
15
10.0
15
4.5
15
4.5
Water-Cooled
Maximum Fuse/
Total Amps
Circuit Breaker
15
15
15
15
15
Part Number: 040005890 Rev 01 06/18
Section 2
6.0
3.0
3.0
10.0
4.0