Set-up/Connections
Combustion Chamber Insert
Venting Connection
Vitorond 100
The vent system must comply with all applicable local
and/or national codes.
If installing boiler with a side wall vent system, ensure
all manufacturer's requirements are met.
Venting codes
For oil-fired boilers install venting system in accordance
with all applicable local codes:. In the absence of local
codes, follow national codes
Local codes or CSA B139-00 in Canada
g
or
NFPA-31 in the U.S.
g
16
Vitorond 100, VR1 40 to 63, 161 to 245 Installation and Service
For optimum, environmentally sound operation, Vitorond
boilers are equipped with a high-grade, corrosion resistant,
stainless steel combustion chamber insert.
Ensure the bolts of the combustion chamber door are
tightened before installing the burner.
Combustion chamber insert sizes
Boiler model No.
a
in.
(mm)
b
in.
(mm)
Building codes
Masonry or concrete or metal chimneys (smokestacks)
shall be constructed according to the requirements of
the province/state building code or, in the absence of
such regulations, in accordance with:
CSA Standard CAN/CSA-A405
g
(National Building Code of Canada) in Canada, or
NFPA 211 (Standard for Chimneys, Fireplaces, Vents,
g
and Solid Fuel-Burning Appliances) in the US. Metal
chimneys also shall meet the requirements of Chapter
4 of NFPA 211.
In Canada, factory built chimneys shall:
Conform to ULC Standards
g
CAN/ULC-S629 for 1202°F (650°C),
CAN/ULC-S604 for Type A, or
CAN/ULC-S609 for Type L chimneys,
Be certified and installed in accordance with the
g
manufacturer's certified instructions, and
Be provided with a clean-out opening that is equipped
g
with a tight-fitting removable cap, and constructed so
that no air can enter the clean-out facility when the cap
is in place.
In the U.S., factory built chimneys shall:
Meet the requirements of NFPA, and
g
Be listed, installed and used in accordance with their
g
listings and manufacturer's instructions.