Installation and commissioning

Using the phasor viewer

Basic setup using the webpages or display

7EN05-0390-00
3. Configure the parameters in Metering Setup > Advanced if appropriate.
Advanced tab
Parameter
PhaseOrder
V4 PT Prim
V4 PT Sec
I4 Prim
I4 Sec
I5 Prim
I5 Sec
Scale Rev Param
Phasor diagrams can help verify or troubleshoot issues with voltage and current
input wiring.
Use ION Setup's Phasor Viewer to display a real-time phasor diagram of the
voltage and current input signals.
1. Start ION Setup then open the Setup assistant for your meter.
2. Select Metering Setup > Phasor.
3. Select Phasor Viewer and click Show.
4. To change the polarity of the voltage or current inputs, click Show Setup to
display the Polarity Settings.
Select the box beside the inputs you want to invert polarity, then click Apply
to Meter.
You can use the meter webpages or display to configure basic metering
parameters.
Using the webpages: Navigate to Setup > Metering.
Using the display: Navigate to Setup Menu > Meter Setup.
Values
Description
ABC, ACB
Power system's rotation order of voltage
phases
1 to 999,999
V4 potential transformer's primary
winding voltage rating
1 to 999,999
V4 potential transformer's secondary
winding voltage rating
1 to 999,999
I4 current transformer's primary winding
current rating
1 to 999,999
I4 current transformer's secondary
winding current rating
1 to 999,999
I5 current transformer's primary winding
current rating
1 to 999,999
I5 current transformer's secondary
winding current rating
ON, OFF
Specifies whether revenue readings are
presented as primary or secondary side
values (ON = primary side, OFF =
secondary side)