Logging

Loss log

The Loss Log (Data Rec 9) is configured to record loss values. Factory settings for this data
recorder:
• Log depth = 3360 records (35 days)
• Interval = 900 seconds (15 minutes)
By default, it logs the following values:
Parameter
MU Ia^2h int
MU Ib^2h int
MU Ic^2h int
MU Vllab^2h int
MU Vllbc^2h int
MU Vllca^2h int
MU Vln a^2h int
MU Vln b^2h int
MU Vln c^2h int

Harmonics logs

Two harmonics logs record various harmonics data, including K-factor and Total Harmonic
Distortion (THD). These recorders are labeled Harm Mean Log and Harm High Log. Factory
settings for these data recorders:
• Log depth = 840 records (35 days)
• Interval = 3600 seconds (1 hour)
By default, they log the following values:
V1 THD mean
V2 THD mean
V3 THD mean
V1 THD high
V2 THD high
V3 THD high
206
Description
Phase A interval current squared hours
Phase B interval current squared hours
Phase C interval current squared hours
Phase A interval voltage Line-to-Line squared hours
Phase B interval voltage Line-to-Line squared hours
Phase C interval voltage Line-to-Line squared hours
Phase A interval voltage Line-to-Neutral squared hours
Phase B interval voltage Line-to-Neutral squared hours
Phase C interval voltage Line-to-Neutral squared hours
Harm Mean Log (Data Rec 7)
I1 THD mean
I2 THD mean
I3 THD mean
Harm High Log (Data Rec 8)
I1 THD high
I2 THD high
I3 THD high
9410 series - User manual
I1 K Fac mean
I2 K Fac mean
I3 K Fac mean
I1 K Fac high
I2 K Fac high
I3 K Fac high
7EN05-0336-09