Electrical installation

9.3.9 To connect the power consumption digital inputs

Installer reference guide
130
A
B
A
B
a Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
Wires: 2 (per input signal)×0.75 mm²
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage
supplied by PCB)
[9.9] Power consumption control.
1 Open the following (see
1 Top panel
2 User interface panel
3 Upper switch box cover
2 Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.
N
X2
X1
A4P
"7.2.6 To open the indoor
L
X2
X1
X2M
a
4
unit" [
 71]):
1
EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1D – 2023.10