Daikin ETSXB16E Installer's Reference Manual

Daikin ETSXB16E Installer's Reference Manual

Hide thumbs Also See for ETSXB16E:
Table of Contents

Advertisement

Quick Links

EPRA14D▲V3▼
EPRA16D▲V3▼
EPRA18D▲V3▼
EPRA14D▲W1▼
EPRA16D▲W1▼
EPRA18D▲W1▼
Installer reference guide
Daikin Altherma 3 H HT ECH₂O
https://daikintechnicaldatahub.eu
ETSH16P30E▲▼
ETSH16P50E▲▼
ETSHB16P30E▲▼
ETSHB16P50E▲▼
ETSX16P30E▲▼
ETSX16P50E▲▼
ETSXB16P30E▲▼
ETSXB16P50E▲▼
▲= A, B, C, ..., Z
▼= , , 1, 2, 3, ..., 9

Advertisement

Table of Contents
loading

Summary of Contents for Daikin ETSXB16E

  • Page 1 Installer reference guide Daikin Altherma 3 H HT ECH₂O https://daikintechnicaldatahub.eu ▲= A, B, C, …, Z EPRA14D▲V3▼ ETSH16P30E▲▼ ▼= , , 1, 2, 3, …, 9 EPRA16D▲V3▼ ETSH16P50E▲▼ EPRA18D▲V3▼ ETSHB16P30E▲▼ EPRA14D▲W1▼ ETSHB16P50E▲▼ EPRA16D▲W1▼ ETSX16P30E▲▼ EPRA18D▲W1▼ ETSX16P50E▲▼ ETSXB16P30E▲▼ ETSXB16P50E▲▼...
  • Page 2: Table Of Contents

    Power limitation activated by digital inputs ....................62 6.6.3 Power limitation process..........................63 6.6.4 BBR16 power limitation..........................64 Setting up an external temperature sensor ........................65 7 Unit installation Installer reference guide EPRA14~18D + ETSH/X(B)16P30+50E Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 3 To connect the WLAN cartridge (delivered as accessory)................139 9.3.15 To connect the solar input ..........................140 9.3.16 To connect the DHW output .......................... 140 EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 4 Symptom: The pump is making noise (cavitation)..................257 14.3.7 Symptom: The pressure relief valve opens....................257 14.3.8 Symptom: The water pressure relief valve leaks................... 258 Installer reference guide EPRA14~18D + ETSH/X(B)16P30+50E Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 5 Wiring diagram: Indoor unit ............................285 16.6 ESP curve: Indoor unit..............................291 16.7 Name plate: Indoor unit ..............................292 17 Glossary 18 Field settings table EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 6: About The Documentation

    Format: Paper (in the box of the indoor unit) ▪ User reference guide: Detailed step-by-step instructions and background information for basic and advanced usage Format: Digital files on https://www.daikin.eu. Use the search function find your model. ▪ Installation manual – Outdoor unit: Installation instructions Format: Paper (in the box of the outdoor unit) ▪...
  • Page 7: Meaning Of Warnings And Symbols

    About the documentation Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
  • Page 8: Installer Reference Guide At A Glance

    General safety precautions Safety instructions that you must read before installing Specific installer safety instructions About the box How to unpack the units and remove their accessories EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 9 Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 10: General Safety Precautions

    WARNING Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY use accessories, optional equipment and spare parts made or approved by Daikin unless otherwise specified. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
  • Page 11: Installation Site

    ▪ Use a separate recovery system so that the unit's compressor does NOT have to operate. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 12 ONLY use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system. ▪ Charge the liquid refrigerant as follows: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 13: Water

    If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 14 Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible. ▪ Over-tightening the terminal screws may break them. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 15 ON and OFF while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 16: Specific Installer Safety Instructions

    WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O...
  • Page 17 After the first filling and before switching on the unit with the mains switch, check whether all electric parts and connection points are dry. In case of freeze protection by glycol: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 18 ▪ Make electrical connections to the fixed wiring. ▪ All components procured on-site and all electrical construction MUST comply with the applicable legislation. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 19 This maximum allowable hot water temperature shall be selected according to the applicable legislation. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 20 If the internal wiring is damaged, it has to be replaced by the manufacturer, its service agent or similarly qualified persons. Troubleshooting (see "14 Troubleshooting" [  253]) DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING/SCALDING EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 21 "7.3.7 To remove the discharge grille, and put the grille in safety position" [  82] DANGER: RISK OF BURNING/SCALDING The water in the storage tank and all the connected piping can be very hot. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 22: About The Box

    To avoid injury, do NOT touch the air inlet or aluminium fins of the unit. Crane Keep the slings within the marked area to not damage the unit. Forklift or pallet truck Enter the pallet from the heavy side. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 23: To Unpack The Outdoor Unit

    After unpacking, carry the unit using the slings attached to the unit. See also: ▪ "4.1.2 To unpack the outdoor unit" [  23] ▪ "7.3.4 To install the outdoor unit" [  78] ±150 4× 4.1.2 To unpack the outdoor unit EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 24: To Remove The Accessories From The Outdoor Unit

    Compressor cover piece f Installation manual – Outdoor unit g Energy label h Discharge grille (upper + lower part) i Installation manual – Discharge grille EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 25: Indoor Unit

    4.2.2 To remove the accessories from the indoor unit 2× 3× 1× 1× 2× 2× 1× 1× 1× 1× 1× 17× 20× 1× 1× 2× 1× 1× 1× 1× 1× 1× EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 26: To Handle The Indoor Unit

    3 Use the handles to carry the unit. 4 After carrying the unit remove the handles, add the screw plugs again and insert the thread covers on the plugs. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 27: About The Units And Options

    Explanation European hydro-split outdoor pair heat pump High water temperature – ambient zone 2 (see operation range) Refrigerant R32 Capacity class Model series Power supply EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 28: Identification Label: Indoor Unit

    Model series 5.3 Combining units and options INFORMATION Certain options may NOT be available in your country. 5.3.1 Possible combinations of indoor unit and outdoor unit EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 29: Possible Options For The Outdoor Unit

    To enable the power saving consumption control by digital inputs you MUST install the demand PCB. For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 30 You can install this LAN adapter to control the system via a smartphone app. For installation instructions, see the installation manual of the LAN adapter and the addendum book for optional equipment. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 31 BIV connector kit (EKECBIVCO*) To make the connection of a bivalent heat source to the bivalent heat exchanger easier, you can install a bivalent connector kit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 32 A solar drainback kit including solar pump and solar controller can be directly connected to the pressureless storage tank of the indoor unit. For installation instructions, see the installation manual of the solar drainback kit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 33: Application Guidelines

    Setting up the storage tank ▪ Setting up the energy metering ▪ Setting up the power consumption control ▪ Setting up an external temperature sensor EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 34: Setting Up The Space Heating/Cooling System

    NOTICE A differential pressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 35: Single Room

    For your daily needs, you can use preset values and schedules. To deviate from your daily needs, you can temporarily overrule the preset values and schedules, or use the holiday mode. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 36 Code: [C-05] heating or cooling demand. Benefits ▪ Wireless. The Daikin external room thermostat is available in a wireless version. ▪ Efficiency. Although the external room thermostat only sends ON/OFF signals, it is specifically designed for the heat pump system. ▪...
  • Page 37 ON/ ▪ #: [2.A] OFF condition. No separation between ▪ Code: [C-05] heating or cooling demand. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 38 ▪ The space operation mode is sent by one digital output (X12M/9 and X12M/10) on the indoor unit to: The heat pump convectors The shut-off valve EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 39: Multiple Rooms - One Lwt Zone

    Human Comfort Interface (BRC1HHDA) or an external room thermostat), while the other rooms are controlled by so-called thermostatic valves, which open or close depending on the room temperature. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 40 Number of water temperature zones: 0 (Single zone): Main ▪ #: [4.4] ▪ Code: [7-02] Benefits ▪ Easy. Same installation as for one room, but with thermostatic valves. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 41 Compared with underfloor heating or radiators for one room: ▪ Comfort. You can set the desired room temperature, including schedules, for each room via the room thermostats. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 42 Code: [C-07] Number of water temperature zones: 0 (Single zone): Main ▪ #: [4.4] ▪ Code: [7-02] Benefits Compared with heat pump convectors for one room: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 43 INFORMATION To increase comfort and performance, we recommend to install the valve kit option EKVKHPC on each heat pump convector. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 44: Multiple Rooms - Two Lwt Zones

    In cooling mode, you can allow the underfloor heating (main zone) to provide refreshment (no real cooling), or NOT allow it. See setup below. Setup Three bizone kit system variations are possible: System without hydraulic separator: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 45 A Additional leaving water temperature zone B Room 1 C Room 2 D Main leaving water temperature zone E Room 3 a Heat pump convectors (+ controllers) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 46 (X12M/19 and X12M/22). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 47 If the main zone must be shut off during cooling mode to prevent condensation on the floor, set it accordingly. "Bizone kit" [  229] for more information on configuration of the bizone kit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 48: Setting Up Bivalent Heat Sources

    OR ▪ external room thermostat control. ▪ Space heating can be done by: The indoor unit An auxiliary boiler (field supply) connected to the system EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 49 Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. ▪ Make sure the return water to the heat pump does NOT exceed 60°C. To do so: Set the desired water temperature via the auxiliary boiler controller to maximum 60°C.
  • Page 50 K1A Auxiliary relay for activation of indoor unit (field supply) K2A Auxiliary relay for activation of boiler (field supply) Indoor Indoor unit Auto Automatic Boiler Boiler EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 51: Setting Up An Indirect Auxiliary Heat Source For Domestic Hot Water And Space Heating

    A Main leaving water temperature zone B One single room a Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat) b Auxiliary boiler (field supply) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 52: Setting Up A Solar System Via Drainback Connection

    Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. ▪ Make sure the return water to the storage tank does NOT exceed 95°C. To do so: Set the desired water temperature via the auxiliary boiler controller to maximum 95°C.
  • Page 53: Setting Up A Solar System Via Bivalent Heat Exchanger

    6.3.4 Setting up a solar system via bivalent heat exchanger Setup 1 Integrate the solar system as follows: a Bivalent heat exchanger IN (red) b Bivalent heat exchanger OUT (blue) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 54: Setting Up An Electric Backup Heater

    Determining the DHW consumption Answer the following questions and calculate the DHW consumption (equivalent hot water volume at 40°C) using typical water volumes: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 55 If energy prices are lower during the night, we recommend to heat up the storage tank during the night. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 56: Setup And Configuration - Storage Tank

    For more information, see "10 Configuration" [  142]. ▪ You can program a schedule to control the DHW pump via the user interface. For more information, see the user reference guide. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 57: Dhw Pump For Disinfection

    Per two hours (for the last 48 hours) Per day (for the last 14 days) Per month (for the last 24 months) Total since installation EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 58: Produced Heat

    INFORMATION When measuring the electrical power consumption, make sure ALL power input of the system is covered by the electrical power meters. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 59: Normal Kwh Rate Power Supply

    Outdoor unit (L d Fuse (L e Indoor unit (L e Outdoor unit (L f Backup heater (L f Indoor unit (L g Backup heater (L EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 60: Preferential Kwh Rate Power Supply

    1 5 0 1 5 0      A Outdoor unit B Indoor unit a Electrical cabinet (L /N): Preferential kWh rate power supply EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 61: Setting Up The Power Consumption Control

    Defrost operation. Otherwise, if defrosting is interrupted several times, the heat exchanger will freeze up. ▪ Space heating and DHW production by allowing the backup heater step 1. ▪ Disinfection operation. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 62: Permanent Power Limitation

    6.6.2 Power limitation activated by digital inputs Power limitation is also useful in combination with an energy management system. The power or current of the entire Daikin system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following: ▪...
  • Page 63: Power Limitation Process

    Example If the configuration is as follows: Power limitation level does NOT allow operation of backup heater (step 1). Then power consumption is limited as follows: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 64: Bbr16 Power Limitation

    Set the power consumption control settings in [9.9] via the user interface (see "Power consumption control" [  215]): Activate BBR16 Set the desired power limitation level EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 65: Setting Up An External Temperature Sensor

    To protect the outdoor unit, the internal sensor of the outdoor unit is always used. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 66: Unit Installation

    Mind the spacing guidelines. See "16.1 Service space: Outdoor unit" [  275]. NOTICE ▪ Do NOT stack the units on each other. ▪ Do NOT hang the unit on a ceiling. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 67 This is to prevent corrosion caused by high levels of salt in the air, which might shorten the life of the unit. Install the outdoor unit away from direct sea winds. Example: Behind the building. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 68 WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O...
  • Page 69: Additional Installation Site Requirements Of The Outdoor Unit In Cold Climates

    Install the indoor unit at a minimum distance of 1 m from other heat sources (>80°C) (e.g. electrical heater, oil heater, chimney) and combustible materials. Otherwise the unit may be damaged or in extreme cases catch fire. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 70 Precise water piping length can be determined using the Hydronic Piping Calculation tool. The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator which can be reached via https://professional.standbyme.daikin.eu. Please contact your dealer if you have no access to Heating Solutions Navigator.
  • Page 71: Opening And Closing The Units

    The transportation stays protect the unit during transport. During installation they must be removed. a Transportation stays (2×) and washers (2×) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 72: To Attach The Compressor Cover Piece

     72]). 5 Remove and discard the transportation stay (b). 7.2.4 To attach the compressor cover piece Required accessory (delivered with the unit): Compressor cover piece EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 73: To Close The Outdoor Unit

    7.2.6 To open the indoor unit NOTICE The top cover can only be removed if the switch box is lowered. Overview a User interface panel b Switch box cover EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 74: To Lower The Switch Box Of The Indoor Unit And Remove The Top Cover

    Prerequisite: The user interface panel has been removed. 1 Loosen the screws. 2 Lift up the switch box. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 75 5 If necessary, remove the top cover. This is necessary in the following cases: ▪ Connecting water piping ▪ Connecting BIV or DB-kit ▪ Connecting backup heater EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 76: To Close The Indoor Unit

    Installing the discharge grille. Protecting the unit against snow and wind by installing a snow cover and baffle plates. See "7.1 Preparing the installation site" [  66]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 77: Precautions When Mounting The Outdoor Unit

    When installing on a pedestal, make sure that the discharge grille still can be put in its safety position. See "7.3.7 To remove the discharge grille, and put the grille in safety position" [  82]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 78: To Install The Outdoor Unit

    To avoid injury, do NOT touch the air inlet or aluminium fins of the unit. 1 Carry the unit by its slings, and put it onto the installation structure. ±150 4× 2 Fix the unit to the installation structure. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 79: To Provide Drainage

    ▪ Install a drain tube heater (field supply). To connect the drain tube heater, see "9.2.1 To connect the electrical wiring to the outdoor unit" [  108]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 80: To Install The Discharge Grille

    Electrical wiring. Before installing the discharge grille, connect the electrical wiring. Install the lower part of the discharge grille 1 Insert the hooks. 2 Insert the ball studs. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 81 4 Align and attach the left side. 5 Align and attach the middle part. 6 Align and attach the right side. 7 Insert the hooks. 8 Insert the ball studs. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 82: To Remove The Discharge Grille, And Put The Grille In Safety Position

    "7.3.7 To remove the discharge grille, and put the grille in safety position" [  82] 1 Remove the upper part of the discharge grille. 4× 2 Remove the lower part of the discharge grille. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 83 4 Align the ball stud and hook on the grille with their counterparts on the unit. 5 Insert the hook. 6 Insert the ball stud. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 84: Mounting The Indoor Unit

    1 Open the screw plug. a Screw plug b Assembly wrench c Spillover connector 2 Insert the spillover connector into the screw plug. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 85 Ensure that any steam or water that may escape is drained in a frost-protected, safe and observable manner. a Pressure relief valve EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 86: Piping Installation

    Inappropriate tooling will cause damage to the pipes. ▪ Insulation. Insulate up to the base of the heat exchanger. ▪ Freeze. Protect against freezing. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 87 Water temperature. All installed piping and piping accessories (valve, connections,…) MUST withstand the following temperatures: INFORMATION The following figure is an example and may NOT completely match your system layout 89°C 70°C 70°C EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 88 See "6.4.4  DHW pump for instant hot water" [  56]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 89: To Check The Water Volume And Flow Rate

    M1…3 Individual motorised valves to control each loop (field supply) Minimum flow rate Check that the minimum flow rate in the installation is guaranteed in all conditions. Minimum required flow rate 12 l/min EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 90: Connecting Water Piping

    Do NOT use excessive force when connecting the field piping and make sure the piping is aligned properly. Deformation of the piping can cause malfunctioning of the unit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 91 Do NOT exceed the maximum tightening torque (Thread size 1", 25-30  N•m). To avoid damage, apply the necessary countertorque with a suitable tool. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 92 Do NOT exceed the maximum tightening torque (Thread size 1", 25-30  N•m). To avoid damage, apply the necessary countertorque with a suitable tool. ≤Ø7 mm EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 93 7 Support the water piping. For rearward facing connections: Support hydraulic lines suitably according to the spatial conditions. This is valid for all water pipes. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 94 A pressure relief valve (field supply) with an opening pressure of maximum 10  bar (=1  MPa) must be installed on the domestic cold water inlet connection in accordance with the applicable legislation. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 95: To Connect A Pressure Vessel

    1 Connect a hose with a non-return valve (1/2") and an external manometer (field supply) to a water tap and the fill and drain valve. Secure the hose against slipping off. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 96 8 Close the fill and drain valve and remove the hose with non-return valve only after air purging is performed and the system is completely filled. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 97: To Protect The Water Circuit Against Freezing

    As a result, the hydraulic components might freeze up after all. Take preventive actions to ensure a minimal exposure of the glycol to air. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 98 When no glycol is added to the water, you can use freeze protection valves at all lowest points of the field piping to drain the water from the system before it can freeze. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 99 NOT insulate the inlet and outlet (release) of these valves. ▪ Do NOT make traps in the field piping. >10 cm >15 cm EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 100: To Fill The Heat Exchanger Inside The Storage Tank

    Before the storage tank can be filled, the heat exchangers inside the storage tank have to be filled, see previous chapters. Fill the storage tank with a water pressure <6 bar and a flow speed <15 l/min. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 101 2 Connect the hose with non-return valve to the fill and drain kit. Follow the steps described in the previous chapter. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 102: To Insulate The Water Piping

    The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator which can be reached via https://professional.standbyme.daikin.eu. Please contact your dealer if you have no access to Heating Solutions Navigator. This recommendation ensures good operation of the unit, however, local regulations may differ and shall be followed.
  • Page 103: Electrical Installation

    ▪ Make electrical connections to the fixed wiring. ▪ All components procured on-site and all electrical construction MUST comply with the applicable legislation. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 104: Guidelines When Connecting The Electrical Wiring

    To prepare stranded conductor wire for installation Method 1: Twisting conductor 1 Strip insulation (20 mm) from the wires. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 105 Screw c Flat washer Stranded conductor wire with round crimp-style terminal a Terminal b Screw c Flat washer Allowed NOT allowed Tightening torques Outdoor unit: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 106: About Electrical Compliance

    OFF mode. At that moment, the outdoor unit compressor will NOT operate. The wiring to the unit is different depending on whether the power supply is interrupted or NOT. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 107: Overview Of Electrical Connections Except External Actuators

    9.1.5 Overview of electrical connections except external actuators NOTICE Unlike to other indoor unit model types, Daikin Altherma 3 * ECH₂O always needs a dedicated power supply for the indoor unit. It is NOT possible to use the interconnection cable as power supply for the indoor unit.
  • Page 108: Connections To The Outdoor Unit

    (optional) Drain tube heater cable (field supply) d Cable sleeves (factory-mounted) 4 Inside the switch box, connect the wires to the appropriate terminals, and fix the cables with cable ties. See: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 109 ▪ Connect the wires to the terminal block (make sure the numbers match with the numbers on the indoor unit) and the earth screw. ▪ Fix the cable with a cable tie. Wires: (3+GND)×1.5 mm² — EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 110 ▪ Fix the cable with cable ties. Wires: (2+GND)×0.75 mm². Wiring must be double insulated. Maximum power allowed for drain tube heater = 115 W (0.5 A) — EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 111 ▪ Connect the wires to the terminal block. ▪ Fix the cable with a cable tie. Wires: 3N+GND Maximum running current: Refer to name plate on unit. — EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 112 ▪ Connect the wires to the terminal block (make sure the numbers match with the numbers on the indoor unit) and the earth screw. ▪ Fix the cable with a cable tie. Wires: (3+GND)×1.5 mm² — EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 113 ▪ Fix the cable with cable ties. Wires: (2+GND)×0.75 mm². Wiring must be double insulated. Maximum power allowed for drain tube heater = 115 W (0.5 A) — EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 114: To Reposition The Air Thermistor On The Outdoor Unit

    9.2.2 To reposition the air thermistor on the outdoor unit This procedure is only necessary in areas with low ambient temperatures. Required accessory (delivered with the unit): Thermistor fixture. Click EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 115: Connections To The Indoor Unit

    For the main zone: ▪ [2.9] Control ▪ [2.A] Ext thermostat type For the additional zone: ▪ [3.A] Ext thermostat type ▪ [3.9] (read-only) Control EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 116 ▪ Installation manual of the remote indoor sensor ▪ Addendum book for optional equipment Wires: 2×0.75 mm² [9.B.1]=2 (External sensor = Room) [1.7] Room sensor offset EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 117: To Connect The Electrical Wiring To The Indoor Unit

    To have easier access to the switch box itself and the routing of cables the switch box can be lowered (see "7.2.6 To open the indoor unit" [  73]). EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 118 All cables which will be connected to the switch box of the ECH O must be fixed by strain relief. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 119: To Connect The Main Power Supply

    2 Connect the main power supply. In case of normal kWh rate power supply Interconnection cable Wires: (3+GND)×1.5 mm² Power supply indoor Wires: 1N+GND unit Maximum running current: 6.3 A EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 120 Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. [9.8] Benefit kWh power supply EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 121: To Connect The Backup Heater Power Supply

    [9.3] Backup heater WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 122 Z less than or equal to Z Connect the backup heater power supply as follows: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 123 Electrical installation Model (power supply) Connections to backup heater power supply *3V (3V: 1N~ 230 V) SWB2 Q1DI 1N~, 50 Hz 230 V AC EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 124: To Connect The Backup Heater To The Main Unit

    1 Open the following (see "7.2.6 To open the indoor unit" [  73]): 1 User interface panel 2 Switch box 3 Switch box cover 4 Top cover EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 125: To Connect The Shut-Off Valve

    2 Connect the valve control cable to the appropriate terminals as shown in the illustration below. NOTICE Wiring is different for a NC (normally closed) valve and a NO (normally open) valve. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 126: To Connect The Electricity Meters

    2 Switch box 3 Switch box cover 4 Top cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 127: To Connect The Domestic Hot Water Pump

    3 Switch box cover 4 Top cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 128: To Connect The Alarm Output

    2 Switch box 3 Switch box cover 4 Top cover 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 129: To Connect The Space Cooling/Heating On/Off Output

    3 Switch box cover 4 Top cover 2 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 130: To Connect The Changeover To External Heat Source

    3 Switch box cover 4 Top cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 131: To Connect The Power Consumption Digital Inputs

    "7.2.6 To open the indoor unit" [  73]): 1 User interface panel 2 Switch box 3 Switch box cover 4 Top cover 2 Install the switch box metal insert. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 132 4 Fix the cable with cable ties to the cable tie mountings. General information, "9.3.1 To connect the electrical wiring to the indoor unit" [  117]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 133: To Connect The Safety Thermostat (Normally Closed Contact)

    3 Fix the cable with cable ties to the cable tie mountings. General information, "9.3.1 To connect the electrical wiring to the indoor unit" [  117]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 134: To Connect A Smart Grid

    ([9.A.2] Electricity meter 2 = None) In case of low voltage Smart Grid contacts Wires (Smart Grid pulse meter): 0.5 mm² Wires (low voltage Smart Grid contacts): 0.5 mm² EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 135 2 Fix the cables with cable ties to the cable tie mountings. In case of high voltage Smart Grid contacts Wires (Smart Grid pulse meter): 0.5 mm² Wires (high voltage Smart Grid contacts): 1 mm² EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 136 1 Install the switch box metal insert. 2 Loosen the cables connected to the terminal of the Smart Grid relay kit (EKRELSG) and remove the terminal. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 137 Electrical installation 3 Install the components of the Smart Grid relay kit as follows: 2× 2× EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 138 X 5M X12M.25 X12M.23 X15M.3 X15M.4 X12M.25 X12M.24 X15M.5 X15M.6 4 Connect the low voltage wiring as follows: 5 Connect the high voltage wiring as follows: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 139: To Connect The Wlan Cartridge (Delivered As Accessory)

    9.3.14 To connect the WLAN cartridge (delivered as accessory) [D] Wireless gateway 1 Insert the WLAN cartridge into the cartridge slot on the user interface of the indoor unit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 140: To Connect The Solar Input

    9.3.16 To connect the DHW output Wires: 2×0.75 mm² Maximum running current: 0.3 A, 230 V AC — 1 Open the following (see "7.2.6 To open the indoor unit" [  73]): EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 141 2 Connect the DHW signal cable as shown in the illustration below. 3 Fix the cable with cable ties to the cable tie mountings. General information, "9.3.1 To connect the electrical wiring to the indoor unit" [  117]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 142: Configuration

    First time – Configuration wizard. When you turn ON the user interface for the first time (via the unit), the configuration wizard starts to help you configure the system. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 143: To Access The Most Used Commands

    Confirm the pin code and proceed. Installer pin code The Installer pin code is 5678. Additional menu items and installer settings are now available. Installer 5678 EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 144 4 Turn the left dial to select the second part of the setting 01 15 5 Turn the right dial to modify the value from 15 to 20. 01 20 EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 145: To Connect The Pc Cable To The Switch Box

    You can find a short overview of the settings in the configuration here. All the settings can also be adjusted in the settings menu (use the breadcrumbs). EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 146 Setpoint mode [2.4] Heating WD curve [2.5] (if applicable) Cooling WD curve [2.6] (if applicable) Schedule [2.1] WD curve type [2.E] Additional zone (only if [4.4]=1) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 147: Possible Screens

    Main menu screen c Lower level screens: c1: Setpoint screen c2: Detailed screen with values c3: Screen with weather-dependent curve c4: Screen with schedule EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 148: Home Screen

    Smart energy is currently being used for domestic hot water. Space operation mode Cooling Heating Outdoor / quiet mode Measured outdoor temperature Quiet mode active Outdoor unit EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 149 Installed heat emitter type: Underfloor heating Fancoil unit Radiator Leaving water temperature setpoint EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 150: Main Menu Screen

    Shows the applicable symbol of your unit. Space heating/ cooling Put the unit in heating mode or cooling mode. You cannot change the mode on heating only models. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 151: Menu Screen

    The setpoint screen is displayed for screens describing system components that need a setpoint value. Examples [1] Room temperature screen [2] Main zone screen °C °C – – Room Main zone EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 152: Detailed Screen With Values

    Selected setting and value Possible actions on this screen Go through the list of settings. Change the value. Go to the next setting. Confirm changes and proceed. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 153: Schedule Screen: Example

    To clear the content of the week schedule 1 Select the name of the current schedule. User defined 1 2 Select Delete. Delete Rename Select 3 Select OK to confirm. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 154 In this example, Monday is the first day you programmed. Thus, the last programmed action is valid up to the first action of next Monday. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 155 5 Repeat this action for all other weekdays. — User defined 1 To program the schedule for Saturday and copy it to Sunday 1 Select Saturday. 2 Select Edit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 156 The schedule name can contain up to 15 characters. 5 Confirm the new name. INFORMATION Not all schedules can be renamed. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 157: Weather-Dependent Curve

    See "10.4.4 Using weather-dependent curves" [  160]. 10.4.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 158: Slope-Offset Curve

    Examples Weather-dependent curve when slope is selected: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 159 The icon corresponds to the heat emitter for that zone: ▪ : Underfloor heating ▪ : Fan coil unit ▪ : Radiator ▪ : Storage tank EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 160: Using Weather-Dependent Curves

    Go to … Main zone – Heating [2.5] Main zone > Heating WD curve Main zone – Cooling [2.6] Main zone > Cooling WD curve EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 161 ↑ Cold Cold ↑ ↑ ↑ ↑ Cold ↓ ↑ ↓ ↑ — ↓ — ↓ Cold ↑ ↓ ↑ ↓ ↓ ↓ ↓ ↓ EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 162: Settings Menu

    No: Room temperature is directly controlled by the user. ▪ Yes: Room temperature is controlled by a schedule and can be modified by the user. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 163 Antifrost function via the backup heater. If the backup heater is not allowed for room frost protection during a U4 error, the room Antifrost setting MUST be disabled. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 164 Room frost protection is guaranteed by the normal logic. ▪ The external room thermostat is "Thermo ON" In case of 2 leaving water temperature zones: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 165 NOTICE When adjusting the room temperature ranges, all desired room temperatures are also adjusted to guarantee they are between the limits. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 166: Main Zone

    [9-0A] Heating comfort setpoint ▪ [3-07]~[3-06]°C [1.9.2] [9-0B] Cooling comfort setpoint ▪ [3-09]~[3-08]°C 10.5.3 Main zone Overview The following items are listed in the submenu: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 167 Define a heating temperature schedule for the main zone via [2.2] Heating schedule. "10.3.7 Schedule screen: Example" [  153]. Cooling schedule Define a cooling temperature schedule for the main zone via [2.3] Cooling schedule. "10.3.7 Schedule screen: Example" [  153]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 168 10°C. Heating WD curve Set weather-dependent heating for the main zone (if [2.4]=1 or 2): EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 169 Note: This value should be lower than [1‑02] as for high outdoor temperatures less warm water is required. Cooling WD curve Set weather-dependent cooling for the main zone (if [2.4]=2): EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 170 It is important to set Emitter type correctly and in accordance with your system layout. The target delta T for the main zone depends on it. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 171 Example underfloor heating: 40–5/2=37.5°C To compensate, you can: ▪ Increase the weather-dependent curve desired temperatures [2.5]. ▪ Enable leaving water temperature modulation and increase the maximum modulation [2.C]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 172 Heating maximum: ▪ [2‑0C]=2 (emitter type main zone = radiator) 37°C~70°C ▪ Else: 37°C~55°C [2.8.3] [9-03] Cooling minimum: ▪ 5°C~18°C [2.8.4] [9-02] Cooling maximum: ▪ 18°C~22°C EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 173 Leaving water temperature: Delta T In heating for the main zone, the target delta T (temperature difference) depends on the selected emitter type for the main zone. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 174 ▪ 3°C~10°C Leaving water temperature: Modulation Only applicable in case of room thermostat control. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 175 See the illustration below. +[8-06] −[8-06] a Weather-dependent curve b Minimum leaving water temperature setpoint required to reach a stable condition on the comfort setpoint for the room. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 176 The weather-dependent curve can be defined using the 2-points method or the Slope-Offset method. "10.4.2 2-points curve" [  157] and "10.4.3 Slope-offset curve" [  158]. Code Description [2.E] ▪ 2-points ▪ Slope-Offset EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 177: Additional Zone

     153]. Setpoint mode The setpoint mode of the additional zone can be independently set from the setpoint mode of the main zone. "Setpoint mode" [  168]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 178 Note: This value should be lower than [0‑01] as for high outdoor temperatures less warm water is required. Cooling WD curve Set weather-dependent cooling for the additional zone (if [3.4]=2): EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 179 2: Radiator The setting of the emitter type has an influence on the space heating setpoint range and the target delta T in heating as follows: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 180 External room thermostat,or Room thermostat. Ext thermostat type Only applicable in external room thermostat control. Also see "10.5.3 Main zone" [  166]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 181: Space Heating/Cooling

    2-points ▪ Slope-Offset 10.5.5 Space heating/cooling INFORMATION Cooling is only applicable in case of reversible models. Overview The following items are listed in the submenu: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 182 While the unit is in operation, the status indicator will light up blue constantly. To set the space operation mode 1 Go to [4.1]: Space heating/cooling > Operation mode EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 183 If the outdoor temperature is between the Space heating off temperature and the Space cooling off temperature, the operation mode remains unchanged. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 184 The space operation only changes from heating to cooling when the room temperature rises above the desired cooling temperature added by the hysteresis value. ▪ Range: 1°C~10°C EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 185 In heating: a Additional LWT zone: Highest temperature b Main LWT zone: Lowest temperature c Mixing station EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 186 ON or OFF condition. Remark: Continuous pump operation requires more energy than sample or request pump operation. a Space heating/cooling control b Off c On d Pump operation EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 187 In this part of the menu it can be read out which type of unit is used: Code Description [4.6] [E‑02] Unit type: ▪ 0 Reversible ▪ 1 Heating only EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 188 6: 80% pump speed during sampling ▪ 7: 70% pump speed during sampling ▪ 8: 60% pump speed during sampling The maximum values depend on the unit type: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 189 Use this setting to compensate for possible heat losses of the building due to the evaporation of melted ice or snow. (e.g. in cold region countries). EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 190: Tank

    Room frost protection [1.4] prevents the room from getting too cold. For more information about room frost protection, see "10.5.2 Room" [  162]. 10.5.6 Tank Overview The following items are listed in the submenu: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 191 When powerful operation is active, the risk of space heating/cooling and capacity shortage comfort problems is significant. In case of frequent domestic hot water operation, frequent and long space heating/cooling interruptions will happen. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 192 ▪ 4: Thursday ▪ 5: Friday ▪ 6: Saturday ▪ 7: Sunday [5.7.3] [2‑02] Start time [5.7.4] [2‑03] Tank setpoint: 60°C [5.7.5] [2‑04] Duration: 40~60 minutes EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 193 During disinfection of the water inside the domestic hot water heat exchanger coil by periodically heating storage tank specific temperature, DHW temperature can exceed this maximum temperature. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 194 Code Description [5.9] [6-00] Heat pump ON hysteresis ▪ 2°C~40°C Setpoint mode Code Description [5.B] Setpoint mode: ▪ Fixed ▪ Weather dependent EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 195 Maximum heat pump temperature at sensor in storage tank HP MAX Heat pump OFF temperature (T −[6-01]) HP OFF HP MAX Heat pump ON temperature (T −[6-00]) HP ON HP OFF EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 196: User Settings

    [7] User settings Space heating/cooling Tank [7.1] Language User settings [7.2] Time/date Information Installer settings [7.3] Holiday [7.4] Quiet [7.5] Electricity price [7.6] Gas price EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 197 ▪ Select On. 2 Set the first day of your holiday. — ▪ Go to [7.3.2]: From. ▪ Select a date. ▪ Confirm the changes. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 198 ▪ You have programmed a quiet mode schedule: During the night: Most quiet. During the day: Off to ensure the heating/cooling capacity of the system. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 199 INFORMATION Price value ranging from 0.00~990 valuta/kWh (with 2 significant values). INFORMATION If no schedule is set, the Electricity price for High is taken into account. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 200 Renewable heat incentive per kWh Calculation of the gas price Gas price=Actual gas price+(Incentive/kWh×0.9) Gas price=4.08+(5×0.9) Gas price=8.58 Calculation of the electricity price Electricity price=Actual electricity price+Incentive/kWh EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 201: Information

    Reset the configuration settings stored in the MMI (user interface of the indoor unit). Example: Energy meterings, holiday settings. INFORMATION This does not reset the configuration settings and field settings of the indoor unit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 202 Return water temperature [°C] Storage tank temperature [°C] Ambient temperature [°C] Leaving water temperature after storage tank [°C] Water pressure [bar] Water volume flow rate [l/min] EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 203: Installer Settings

    [8.B] Piping diagram Real-time sensor and actuator information of the main system components 10.5.9 Installer settings Overview The following items are listed in the submenu: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 204 This setting is read only. Code Description [9.2.1] [E‑05] ▪ Integrated [E‑06] The backup heater will also be used for domestic hot water heating. [E‑07] EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 205 When measuring the resistance value of each heater, you can set the exact heater capacity and this will lead to more accurate energy data. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 206 If the storage temperature setpoint is higher than 50°C and no auxiliary boiler is installed, Daikin recommends NOT to disable the backup heater second step because it will have a big impact on the required time for the unit to heat up the storage tank.
  • Page 207 The backup heater will ONLY assist if you increase the equilibrium temperature [5‑01] to the required ambient temperature you need to reach the higher setpoint. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 208 Malfunctioning main menu screen. To keep energy consumption low, we recommend to set Emergency to auto SH reduced/DHW off if the house is unattended for longer periods. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 209 This is important in case glycol is used to protect the water circuit against freezing. If NOT set correctly, the liquid in the piping can freeze. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 210 [8-02]: Anti-recycle timer [8-01] [8-02] 1 Heat pump domestic water heating mode (1=active, 0=not active) 2 Hot water request for heat pump (1=request, 0=no request) t Time EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 211 Range: 0~95 minutes Water pipe freeze prevention Only relevant for installations with water piping outdoors. This function tries to protect outdoor water piping from freezing. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 212 In case of room buffering, the room will heat up or cool down to the comfort setpoint. In case of tank buffering, the tank will heat up to the maximum tank temperature. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 213 Restriction: Only applicable if [9.8.4] is NOT set to Smart Grid. Allow pump: ▪ 0 No: Pump is forced off ▪ 1 Yes: No limitation EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 214 See also below table (Smart Grid operation modes). [9.8.6] Restriction: Only applicable if [9.8.4]=Smart Grid. To set if electrical heaters are allowed. Allow electrical heaters: ▪ ▪ EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 215 2 Inputs: Enabled: You can set up to four different power limitation values (in A or kW) to which the system power consumption will be limited when the corresponding digital input asks. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 216 Limits when [9.9.1]=Inputs and [9.9.2]=kW: Code Description [9.9.9] [5-09] Limit 1: 0 kW~20 kW [9.9.A] [5-0A] Limit 2: 0 kW~20 kW [9.9.B] [5-0B] Limit 3: 0 kW~20 kW [9.9.C] [5-0C] Limit 4: 0 kW~20 kW EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 217 (BBR16 activation and BBR16 power limit). After 2 weeks, the unit freezes these settings. Note: This is different from the permanent power limitation, which is always changeable. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 218 ▪ 0 None: NOT installed ▪ 1 1/10kWh: Installed ▪ 2 1/kWh: Installed ▪ 3 10/kWh: Installed ▪ 4 100/kWh: Installed ▪ 5 1000/kWh: Installed EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 219 The outdoor temperature is averaged over the selected time period. Code Description [9.B.3] [1-0A] Averaging time: ▪ 0: No averaging ▪ 1: 12 hours ▪ 2: 24 hours ▪ 3: 48 hours ▪ 4: 72 hours EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 220 INFORMATION Direct (SH) is only possible in case of 1 leaving water temperature zone with: ▪ room thermostat control, OR ▪ external room thermostat control. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 221 To determine the value of [C‑03], proceed as follows: 1 Determine the COP (= coefficient of performance) using the formula: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 222 Code Description [7.5.1] User settings > Electricity price > High [7.5.2] User settings > Electricity price > Medium [7.5.3] User settings > Electricity price > EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 223 EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 224 Manually start a defrost operation. The forced defrost will only start when at least the following conditions are fulfilled: ▪ Unit is in heating operation and has been running for a few minutes EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 225 2 On the user interface, go to [9.N] Export MMI settings. 3 Select OK. 4 Remove the USB memory stick and close the user interface — panel. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 226 HP! HP more efficient according to efficiency calculation for space heating B! Boiler more efficient according to efficiency calculation for space heating B:on Boiler on B:OK Boiler on allowed Support Tank state: Support EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 227 Range: 0 kW~63 kW (step: 1 kW) The capacity should be limited to the capacity provided by the heat pump. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 228 Equilibrium temperature: Outdoor temperature below which operation of the backup heater (and tank heating support in case of a bivalent system) is allowed. Range: –15°C~35°C EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 229 0 No : The system only has a main zone. ▪ 1 N/A ▪ 2 Yes: A bizone kit is installed in order to add an additional temperature zone. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 230 The speed of the main zone pump can be fixed with this setting. Code Description [9.P.4] [7-0B] Main zone pump fixed PWM: Fixed pump speed for main (mixed) zone. ▪ 20~95% (default: 95) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 231: Commissioning

     237] 10.5.11 User profile [B] User profile: See "To change the user permission level" [  143]. [B] User profile Installer settings Commissioning User profile Operation Malfunctioning EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 232: Operation

    The user can then control the system via the ONECTA app. This needs the following components in case of WLAN cartridge: This needs the following components in case of WLAN module: EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 233 ONECTA app. Remove from cloud: Remove the WLAN cartridge/module from the cloud. Code Description [D.4] Remove from cloud: ▪ ▪ EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 234 Connected to [WLAN_SSID] Cloud connection: Read out the status of the connection to the cloud. Code Description [D.6] Cloud connection: ▪ Not connected ▪ Connected EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 235: Menu Structure: Overview User Settings

    (**) Only accessible by installer (***) Only applicable when WLAN is installed INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 236: Menu Structure: Overview Installer Settings

    Mixing valve turning time (*) Only applicable in Swedish language. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 237: Commissioning

    11 Commissioning NOTICE General commissioning checklist. Next to the commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Business Portal (authentication required). The general commissioning checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during commissioning and hand-over to the user.
  • Page 238: Precautions When Commissioning

    There are NO loose connections or damaged electrical components in the switch box. There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 239: Checklist During Commissioning

    . If the flow rate is too low: — ▪ Do air purge. ▪ Check the function of the valve motor of M1S and M2S. Replace the valve motor if necessary. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 240: Air Purge Function

    Finally open the two manual air purging valves and check if the circuit is sufficiently filled with water. The air purge function automatically stops after 30 minutes. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 241 To change these settings during the air purge, open the menu and go to [A.3.1.5]: Settings. ▪ Scroll to Circuit and set it to Space/Tank. ▪ Scroll to Pump speed and set it to Low/High. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 242: Operation Test Run

    Result: The test run starts. It stops automatically when ready (±30 min). To stop the test run manually: — 1 In the menu, go to Stop test run. 2 Select OK to confirm. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 243: Actuator Test Run

    Make sure that all air is purged before executing the test run. Also avoid disturbances in the water circuit during the test run. ▪ Shut off valve test EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 244: Underfloor Heating Screed Dryout

    1 the duration in hours, up to 72 hours, 2 the desired leaving water temperature, up to 55°C. Example: 24h (1) 36h (2) 35°C (2) 25°C (1) T Desired leaving water temperature (15~55°C) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 245 [D‑01]=0 ▪ [4‑08]=0 ▪ [4‑01]≠1 Steps Conditions: An underfloor heating screed dryout schedule has been programmed. "To program an underfloor heating screed dryout schedule" [  244]. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 246 1 Go to [A.4.3]: Commissioning > UFH screed dryout > Status 2 You can read out the value here: Stopped at + the step — where the underfloor screed dryout was stopped. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 247: To Set Up Bivalent Heat Sources

    [C-02] set to 0. HINT: If field code [C-02] is set to 0 and no backup heater is connected, error UA 17 is output at AL 3 * ECH2O. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 248: Hand-Over To The User

    Show the user what to do for the maintenance of the unit. ▪ Explain about energy saving tips to the user as described in the operation manual. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 249: Maintenance And Service

    Before performing any maintenance or service work, touch a metal part of the unit in order to eliminate static electricity and to protect the PCB. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 250: Yearly Maintenance

    Storage tank water level 13.3.4 Yearly maintenance indoor unit: instructions Water pressure – Space heating/cooling circuit Keep water pressure above 1 bar. If it is lower, add water. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 251 2 Switch box 2 Check if the red level indicator is visible. If NOT, add water to the storage tank (see "8.2.8 To fill the storage tank" [  100]). EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 252 Maintenance and service EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 253: Troubleshooting

    Carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring. 14.2 Precautions when troubleshooting DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING/SCALDING EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 254: Solving Problems Based On Symptoms

    In some cases, it is normal that the unit decides to use a low water flow. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 255: Symptom: Hot Water Does Not Reach The Desired Temperature

    Forced off contact. If Forced off contact is On, the unit is operating under the preferential kWh rate. Wait for the power to return (maximum 2 hours). EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 256: Symptom: The System Is Making Gurgling Noises After Commissioning

    If yes, make sure that the room where you want to purge air is sufficiently ventilated. Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 257: Symptom: The Pump Is Blocked

    14.3.7 Symptom: The pressure relief valve opens Possible causes Corrective action The valve (if equipped) of the water Open the valve. circuit towards the expansion vessel is closed. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 258: Symptom: The Water Pressure Relief Valve Leaks

    ▪ the boiler is operating correctly. ▪ the boiler capacity is sufficient. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 259: Symptom: Tank Disinfection Function Is Not Completed Correctly (Ah-Error)

    This should be done by a licensed installer or by your local dealer. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 260: To Display The Help Text In Case Of A Malfunction

    Water flow problem. Pump deblocking active 7H-08 Pump abnormality during operation (pump feedback) 80-01 Returning water temperature sensor problem 81-00 Leaving water temperature sensor problem 81-01 Mixed water thermistor abnormality. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 261 Heat exchanger thermistor abnormality CJ-02 Room temperature sensor problem E1-00 OU: PCB defect E2-00 Leakage current detection error E3-00 OU: Actuation of high pressure switch (HPS) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 262 J6-32 Leaving water temperature thermistor Abnormality (outdoor unit) J6-33 Sensor communication error J8-00 Malfunction of refrigerant liquid thermistor JA-00 OU: Malfunction of high pressure sensor EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 263 MMI/bizone kit communication problem U8-07 P1P2 communication error U8-09 MMI software version {version_MMI_software} / Indoor unit [version_IU_modelname] compatibility error U8-11 Connection with the Wireless gateway lost EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 264 If the software is not successfully updated then you must make sure that your USB device has the FAT32 format. INFORMATION The user interface will display how to reset an error code. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 265: Disposal

    See: ▪ "7.3.6 To install the discharge grille" [  80] ▪ "7.3.7 To remove the discharge grille, and put the grille in safety position" [  82] EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 266: To Manually Open The Electronic Expansion Valves

    3 Turn the EEV magnet anticlockwise to the fully open position of the valve. If you are not sure about what the open position is, turn the valve in its middle position so that refrigerant can pass. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 267: Recovery Mode - In Case Of Epra-Dav3* And Epra-Daw1* Models (7-Leds Display)

    Press BS1 once. H1P keeps flashing, indicating that you are in a mode that does not allow compressor operation. = OFF, = ON, and = flashing. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 268 / solenoid valves to their initial state. INFORMATION Power OFF. When power is turned OFF and turned ON again, the recovery mode is deactivated automatically. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 269: Recovery Mode - In Case Of Epra-Dbw1* Models (7-Segments Display)

    Display the current value. Press BS3 once. Change the value to 2. Press BS2 once. Enter the value in the system. Press BS3 once. Confirm. Press BS3 once. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 270 Result: The recovery mode is deactivated. The unit returns the electronic expansion valves to their initial state. INFORMATION Power OFF. When power is turned OFF and turned ON again, the recovery mode is deactivated automatically. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 271: To Drain The Storage Tank

    Connection cover b Screw plug 3 Insert the screw plug into the fill and drain kit and secure with the clip contained in the option kit. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 272 1 Place an appropriate tray under the drain connection to collect water spillage. 2 Open the screw plug and remove the sealing plug and IMMEDIATELY close with the previously prepared screw plug with drain connection. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 273: To Drain The Storage Tank With A Connected Pressureless Solar System

    Sealing plug c Fill and drain kit 5 Open the valve of the fill and drain kit. 6 Switch the drain connection valve to standard position. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 274: Technical Data

    Technical data 16 Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). In this chapter 16.1...
  • Page 275: Service Space: Outdoor Unit

    Height of obstacles B and D NOT allowed NOTICE Cascading outdoor units. Installation layouts with multiple outdoor units in combination with floor-standing indoor units are NOT allowed. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 276: Piping Diagram: Outdoor Unit

    Y3E Electronic expansion valve (injection) Y1S Solenoid valve (4-way valve) Y2S Solenoid valve (low pressure bypass) Y3S Solenoid valve (hot gas bypass) Y4S Solenoid valve (liquid injection) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 277: Piping Diagram: Indoor Unit

    R2T Thermistor (backup heater – water OUT) R5T, R8T Thermistor (tank) R7T Thermistor (tank - water OUT) S1L Flow switch Screw connection Flare connection Quick coupling Brazed connection EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 278: Wiring Diagram: Outdoor Unit

    Right side view See note *** See note *** Notes: Symbols: Live Neutral Protective earth Noiseless earth Field wiring Option Terminal strip Terminal Connector Connection EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 279 Push button switch C1~C4 (A1P, A2P) Capacitor DS1 (A1P) DIP switch Drain tube heater (field supply) E1HHEX~E3HHEX Plate heat exchanger heaters Field fuse (field supply) EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 280 High pressure sensor S1PH, S2PH High pressure switch S1PL Low pressure switch Current transfo TC (A2P) Signal transmission circuit V1D~V4D (A1P) Diode V1R (A1P) IGBT power module EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 281 K3R (A1P) Magnetic relay (Y3S) K4R (A1P) Magnetic relay (E1HC) K2M, K11M (A2P) Magnetic contactor L1R~L4R Reactor Compressor motor Fan motor PS (A2P) Switching power supply EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 282 Printed circuit board (ACS) BS1~BS3 (A1P) Push button switch C1~C619 (A1P) Capacitor DS1 (A1P) DIP switch Drain tube heater (field supply) E1HHEX Plate heat exchanger heater EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 283 High pressure switch S1PL Low pressure switch SEG* (A1P) 7-segment display Current transfo TC (A1P) Signal transmission circuit V1D~V3D (A1P) Diode V1R, V2R (A1P) Diode module EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 284 Solenoid valve (4‑way valve) Solenoid valve (low pressure bypass) Solenoid valve (hot gas bypass) Solenoid valve (liquid injection) Z1C~Z11C Noise filter (ferrite core) Z1F~Z5F (A1P, A2P) Noise filter EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 285: Wiring Diagram: Indoor Unit

     Safety thermostat  Safety thermostat Main LWT Main leaving water temperature  On/OFF thermostat (wired)  On/OFF thermostat (wired)  On/OFF thermostat (wireless)  On/OFF thermostat (wireless)  Ext. thermistor  External thermistor EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 286 # Domestic hot water pump # 2-way valve for cooling mode PC (A15P) * Power circuit Thermal protector backup heater # Safety thermostat Q*DI # Earth leakage circuit breaker EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 287 Alarm output Alarm output BUH option Backup heater option BUH option only for * Backup heater option only for * Bizone mixing kit Bizone mixing kit EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 288 Space C/H On/OFF output Space cooling/heating On/OFF output SWB1 Switch box (4) Option PCBs (4) Option PCBs Only for demand PCB option Only for demand PCB option EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 289 Only for wireless On/OFF thermostat Only for wireless On/OFF thermostat (6) Backup heater power supply (6) Backup heater power supply Only for *** Only for *** SWB2 Switch box EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 290 Power limitation A8P: X801M: 4-5 user interface communication demand input 4 signal 2 core 2x0.75 Only for LAN adapter A13P: P1-P2 user interface communication 4D132247 D EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 291: Esp Curve: Indoor Unit

    See also the minimum and maximum allowed water flow range in the technical specifications. ▪ Make sure water quality complies with EU directive 2020/2184. EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 292: Name Plate: Indoor Unit

    Max. operating pressure PMS (drinking water installation) m Nominal voltage U n Rated current of fuse o Protection type p Backup heater (optional) q Part number r Revision EPRA14~18D + ETSH/X(B)16P30+50E Installer reference guide Daikin Altherma 3 H HT ECH₂O 4P679467-1C – 2023.07...
  • Page 293: Glossary

    Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
  • Page 294: Field Settings Table

    1/19 Field settings table Applicable indoor units ETSH16P30E▲▼ ETSH16P50E▲▼ ETSHB16P30E▲▼ ETSHB16P50E▲▼ ETSX16P30E▲▼ ETSX16P50E▲▼ ETSXB16P30E▲▼ ETSXB16P50E▲▼ Notes (*1) *X* (*2) *H* (*3) (*4) EKECBUA3V (*5) EKECBUA6V (*6) EKECBUA9W BUH less (*7) 300L tank (*8) E model (*E▲) (*9) E7 model (*E▲7) (*10) ▲...
  • Page 295 2/19 Field settings table Breadcrumb Setting name Range, step Default value Room └─ Antifrost 1.4.1 [2-06] Activation 0: No 1: Yes 1.4.2 [2-05] Room setpoint 4~16°C, step: 1°C 8°C └─ Setpoint range 1.5.1 [3-07] Heating minimum 12~18°C, step: 1°C 12°C 1.5.2 [3-06] Heating maximum...
  • Page 296 3/19 Field settings table Breadcrumb Setting name Range, step Default value [2-0C] Emitter type 0: Underfloor heating 1: Fancoil unit 2: Radiator └─ Setpoint range 2.8.1 [9-01] Heating minimum 15~37°C, step: 1°C 25°C 2.8.2 [9-00] Heating maximum R/W ([2- [2-0C]=2: 0C] ≠...
  • Page 297 4/19 Field settings table Breadcrumb Setting name Range, step Default value [0-02] High ambient temp. for LWT add zone heating WD curve. 10~25°C, step: 1°C 15°C [0-03] Low ambient temp. for LWT add zone heating WD curve. -40~5°C, step: 1°C -15°C └─...
  • Page 298 5/19 Field settings table Breadcrumb Setting name Range, step Default value [9-0D] Pump speed limitation 0~8, step:1 0 : No limitation 1~4 : 90~60% pump speed 5~8 : 90~60% pump speed during sampling 6 80% pump speed Space heating / cooling [F-00] Pump outside range 0: Restricted...
  • Page 299 6/19 Field settings table Breadcrumb Setting name Range, step Default value [6-01] Margin 0~10°C, step: 1°C 0°C WD curve type 0: 2-points 1: Slope-Offset User settings └─ Quiet 7.4.1 mode 0: OFF 1: Manual 2: Automatic 7.4.3 Level 0: Quiet 1: More Quiet 2: Most Quiet └─...
  • Page 300 7/19 Field settings table Breadcrumb Setting name Range, step Default value 9.1.4.4 [6-04] Additional capacity step 2 R/W (*5, 0~10kW, step: 0,2kW 0kW (*4) R/O (*4, 3kW (*7) 4kW (*5) 6kW (*6) └─ Main zone 9.1.5.1 [2-0C] Emitter type 0: Underfloor heating 1: Fancoil unit 2: Radiator 9.1.5.2...
  • Page 301 8/19 Field settings table Breadcrumb Setting name Range, step Default value 9.1.9 [0-00] Leaving water value for high ambient temp. for LWT add zone [9-05]~min(45,[9-06])°C, step: 1°C heating WD curve. [2-0C]=0 25°C [2-0C]=1 35°C [2-0C]=2 35°C 9.1.9 [0-01] Leaving water value for low ambient temp. for LWT add zone [9-05]~[9-06]°C, step: 1°C heating WD curve.
  • Page 302 9/19 Field settings table Breadcrumb Setting name Range, step Default value 9.3.4 [6-03] Capacity step 1 0~10kW, step: 0,2kW 2kW (*5) 3kW (*4, *6, *7) 9.3.5 [6-04] Additional capacity step 2 R/W (*5, 0~10kW, step: 0,2kW 0kW (*4) R/O (*4, 3kW (*7) 4kW (*5) 6kW (*6)
  • Page 303 10/19 Field settings table Breadcrumb Setting name Range, step Default value 9.8.4 [D-01] Benefit kWh power supply 0: No 1: Open 2: Closed 3: Smart Grid 9.8.6 Allow electric heaters 0: No 1: Yes 9.8.7 Enable Room buffering 0: No 1: Yes 9.8.8 Limit setting kW...
  • Page 304 11/19 Field settings table Breadcrumb Setting name Range, step Default value 9.B.3 [1-0A] Averaging time 0: No 1: 12 h 2: 24 h 3: 48 h 4: 72 h └─ Bivalent 9.C.1 [C-02] Bivalent 0: Off 1: Direct (SH) 2: Indirect (DHW) (*3) 3: Indirect (DHW + SH) 9.C.2 [7-05]...
  • Page 305 12/19 Field settings table Breadcrumb Setting name Range, step Default value [0-0D] High ambient temp. for DHW WD curve. 10~25°C, step: 1°C 15°C [0-0E] Low ambient temp. for DHW WD curve. -40~5°C, step: 1°C -10°C [1-00] Low ambient temp. for LWT main zone heating WD curve. -40~5°C, step: 1°C -15°C [1-01]...
  • Page 306 13/19 Field settings table Breadcrumb Setting name Range, step Default value [2-00] When should the disinfection function be executed? 0: Each day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday [2-01] Should the disinfection function be executed? 0: No 1: Yes [2-02]...
  • Page 307 14/19 Field settings table Breadcrumb Setting name Range, step Default value [4-03] Operation permission of the booster heater. 0: Restricted 1: Allowed 2: Overlap 3: Compressor off 4: Legionella only [4-04] Water pipe freeze prevention 0: Continuous pump operation 1: Non continuous pump operation 2: OFF [4-05] [4-06]...
  • Page 308 15/19 Field settings table Breadcrumb Setting name Range, step Default value [6-01] The temperature difference determining the heat pump OFF 0~10°C, step: 1°C temperature. 0°C [6-02] What is the capacity of the booster heater? 0~10kW, step: 0,2kW [6-03] What is the capacity of the backup heater step 1? 0~10kW, step: 0,2kW 2kW (*5) 3kW (*4, *6, *7)
  • Page 309 16/19 Field settings table Breadcrumb Setting name Range, step Default value [8-03] Booster heater delay timer. 20~95 min, step: 5 min 50 min [8-04] Additional running time for the maximum running time. 0~95 min, step: 5 min 95 min [8-05] Allow modulation of the LWT to control the room temp? 0: No 1: Yes...
  • Page 310 17/19 Field settings table Breadcrumb Setting name Range, step Default value [C-02] Is an external backup heat source connected? 0: Off 1: Direct (SH) 2: Indirect (DHW) (*3) 3: Indirect (DHW + SH) [C-03] Bivalent activation temperature. -25~25°C, step: 1°C 0°C [C-04] Bivalent hysteresis temperature.
  • Page 311 18/19 Field settings table Breadcrumb Setting name Range, step Default value [D-0A] [D-0B] [D-0C] [D-0D] [D-0E] [E-00] Which type of unit is installed? 0: LT split [E-01] Which type of compressor is installed? [E-02] What is the indoor unit software type? R/W (*1) 0: Reversible (*1) R/O (*2)
  • Page 312 19/19 Field settings table Breadcrumb Setting name Range, step Default value [F-0C] Close shut-off valve during cooling? 0: No (*10) 1: Yes (*9) [F-0D] What is the pump operation mode? 0: Continuous 1: Sample 2: Request [F-0E] Tank heating support_max 10~35 kW, step: 1kW 20 kW Bi-zone kit settings...
  • Page 316 4P679467-1C 2023.07 Verantwortung für Energie und Umwelt...