Figure 39. wiring locations and connection ports

Tracer TU

The AdaptiView™ TD7 operator interface allows for daily operational tasks and setpoint changes.
However, to adequately service chillers, Tracer
nel, contact your local Trane office for software purchase information.) Tracer TU adds a level of
sophistication that improves service technician effectiveness and minimizes chiller downtime.
This portable PC-based service-tool software supports service and maintenance tasks, and is
required for software upgrades, configuration changes and major service tasks.
Tracer TU serves as a common interface to all Trane chillers, and will customize itself based on
the properties of the chiller with which it is communicating. Thus, the service technician learns
only one service interface.
The panel bus is easy to troubleshoot using LED sensor verification. Only the defective device is
replaced. Tracer TU can communicate with individual devices or groups of devices.
All chiller status, machine configuration settings, customizable limits, and up to 100 active or
historic diagnostics are displayed through the service-tool software interface.
LEDs and their respective Tracer TU indicators visually confirm the availability of each connected
sensor, relay, and actuator.
Tracer TU is designed to run on a customer's laptop, connected to the Tracer AdaptiView control
panel with a USB cable. Your laptop must meet the following hardware and software require-
ments:
RTHD-SVX04K-EN
P1
BACnet MS/TP or
MODBUS RTU
USB Ports (x4)
Wi-Fi Module,
LON U60 module,
USB stick
1 GB RAM (minimum)
1024 x 768 screen resolution
CD-ROM drive
Ethernet 10/100 LAN card
An available USB 2.0 port
Windows 7 Enterprise or Professional operating system (32-bit or 64-bit)
Note: Tracer TU versions 8.6 and earlier will also support Microsoft® Windows® XP Profes-
sional operation system with Service Pack 3 (SP3) .
P2
P3
MODBUS
IPC3
Master
(LLIDs)
Micro SD Card
Ethernet Port 1
Slot Backup and
BACnet/IP ,
restore
MODBUS TCP ,
TIS
®
TU service tool is required. (Non-Trane person-
Operator Interface Controls
IMC
Wi-Fi, WCI's,
Optional XM
Ethernet Port 2
TD7 or TD12
Hardware