AVIOTEC 8000i IR
4.1

Smoke detection (real smoke)

Figure 4.2: Test setup (smoke detection, real smoke generated by smoke cartridges)
1.
2.
3.
ð
Enter the results in the commissioning report.
Bosch Sicherheitssysteme GmbH
Put the fireproof metal bucket on solid and fireproof ground.
Position two smoke cartridges upright into the metal bucket.
Ignite the smoke cartridges with a stick lighter or via electric smoke cartridge ignition.
The smoke detector should trigger the alarm within 60 s, depending on the verification
time used.
Commissioning
Test procedure | en
2023-10 | 01 | F.01U.414.170
9