4.3

Flame detection (test video)

Figure 4.4: Test setup (flame detection, test video)
1.
2.
3.
ð
Enter the results in the commissioning report.
Bosch Sicherheitssysteme GmbH
Place a playback device (computer monitor or a tablet computer) in the detection area
in front of the camera.
Align the monitor to the test camera.
Play the video for flame detection.
A flame alarm shall be triggered within the set flame verification time plus 15 s. A
connected video client shall show a rectangular box around the flame region.
Commissioning
Test procedure | en
11
2023-10 | 01 | F.01U.414.170