Test Procedure - Bosch AVIOTEC 8000i IR Commissioning

Hide thumbs Also See for AVIOTEC 8000i IR:
Table of Contents

Advertisement

8
en | Test procedure
4

Test procedure

Preparation of the test scene
Ensure that the camera is properly installed. For functional testing, existing fire alarm
systems and detectors must be switched to revision mode. This also applies to fire alarm
systems in which the customer might have integrated the camera directly to the fire panel.
Settings in the camera menu
See operation manual for detailed description.
Figure 4.1: Moiré effect caused by two superimposed patterns (example)
After the tests
2023-10 | 01 | F.01U.414.170
Identify an appropriate and clearly visible place in the detection area of the camera.
Remove combustible material from the test area.
Make sure that only authorized persons have access to the test area.
The playback device and the camera must be mounted stable and may not vary during
the test.
In bright environmental conditions use a monitor hood.
Make sure no scattering light falls to the screen.
Place the monitor at a position in the room where flame and/or smoke video is clearly
visible on the camera live image. The flame and/or smoke displayed on the monitor
should have a size of at least 5 to 10% of the camera image.
Remove all masks in the detection settings, or test in an area of the image where no
mask is applied.
Activate flame and smoke detector settings and select size and verification times that
are required for the scene.
Start the lens wizard and focus on the screen, if necessary.
If there is flickering in the camera video image, activate ALC mode 50 Hz or 60 Hz.
Choose an option that reduces the flickering best.
Patterns in the camera image can lead to image interferences caused by the Moiré
effect. A Moiré pattern is the result of two superimposed patterns visible on the screen.
In this case, adjust the lens settings accordingly, until the Moiré effects disappear.
Restart the camera (reset automask storage)
Remove the screen and adjust the camera to the surveillance scene again
Start the lens wizard and focus on the scene, if necessary.
Select the appropriate ALC mode.
+
Commissioning