12 Specific data IO-Link (pin 6)

12.2 Process data

The motorized linear actuator has access to process data via the IO-Link. This is transmitted in cycles with every IO-Link tele-
gram.
Master → Device
Name
Drive go Open
Drive go Close
Start Initialization
Locate
Device → Master
Name
Valve position Open
Valve position Close
Operating mode
GEMÜ 543 eSyStep
OPEN / CLOSE (Code AE)
Bit
0
0 → Actuator does not move into position Open
1 → Actuator moves into position Open
1
0 → Actuator does not move into position Closed
1 → Actuator moves into position Closed
2
0 → Normal operation
1 → Initialization mode
3
0 → Off
1 → On
Bit
0
0 → Process valve not in Open position
1 → Process valve in Open position
1
0 → Process valve not in Closed position
1 → Process valve in Closed position
2
0 → Normal operation
1 → Initialization mode